6-178
IM 05P07A01-01EN
6.6 GREEN Series Compatible D Registers
Loop-2 Alarm-1 setpoint to Alarm-8 setpoint of Groups 3
When D0957 (AL3.2) = 4, 6, 14, 16, 34, 44, 36, 46
Symbol
Event
GREEN Series
UTAdvanced
D0504
1.A3
A3_L2_1 (D3606)
The sign of the alarm setpoint is reversed and is set to UTAdvanced.
(Example: 1.A3=10 → 1.A3=-10)
D0529
2.A3
A3_L2_2 (D3626)
D0554
3.A3
A3_L2_3 (D3646)
D0579
4.A3
A3_L2_4 (D3666)
D0604
5.A3
A3_L2_5 (D3686)
D0629
6.A3
A3_L2_6 (D3706)
D0654
7.A3
A3_L2_7 (D3726)
D0679
8.A3
A3_L2_8 (D3746)
Loop-2 Alarm-1 setpoint to Alarm-8 setpoint of Groups 4
When D0958 (AL4.2) = 4, 6, 14, 16, 34, 44, 36, 46
Symbol
Event
GREEN Series
UTAdvanced
D0505
1.A4
A4_L2_1 (D3607)
The sign of the alarm setpoint is reversed and is set to UTAdvanced.
(Example: 1.A4=10 → 1.A4=-10)
D0530
2.A4
A4_L2_2 (D3627)
D0555
3.A4
A4_L2_3 (D3647)
D0580
4.A4
A4_L2_4 (D3667)
D0605
5.A4
A4_L2_5 (D3687)
D0630
6.A4
A4_L2_6 (D3707)
D0655
7.A4
A4_L2_7 (D3727)
D0680
8.A4
A4_L2_8 (D3747)
D0915 to D0918: Loop-1 alarm-1 type to alarm-4 type
UTAdvanced
Register
No.
Description
Range and meaning of value
D0915
AL1.T_L1
Loop-1 alarm-1 type
0: Disable
01: PV high limit
02: PV low limit
03: SP high limit
04: SP low limit
05: Deviation high limit
06: Deviation low limit
07: Deviation high and low limits
08: Deviation within high and low limits
09: Target SP high limit
10: Target SP low limit
11: Target SP deviation high limit
12: Target SP deviation low limit
13: Target SP deviation high and low limits
14: Target SP deviation within high and low limits
15: OUT high limit
16: OUT low limit
17: Cooling-side OUT high limit
18: Cooling-side OUT low limit
19: Analog input PV high limit
20: Analog input PV low limit
21: Analog input RSP high limit
22: Analog input RSP low limit
23: Analog input AIN2 high limit
24: Analog input AIN2 low limit
25: Analog input AIN4 high limit
26: Analog input AIN4 low limit
27: Feedback input high limit
28: Feedback input low limit
29: PV velocity
30: Fault diagnosis
31: FAIL
D0916
AL2.T_L1
Loop-1 alarm-2 type
D0917
AL3.T_L1
Loop-1 alarm-3 type
D0918
AL4.T_L1
Loop-1 alarm-4 type