6-106
IM 05P07A01-01EN
6.4 UT55A/UT52A/UP55A D Registers
Register
No.
Description
Range and meaning of value
D6201
AL1.S
AL1 function selection
Set an I relay number (Setting range: 4001 to 6000,
UP55A: 4001 to 6304).
Ex.) Set the number 4353 for AL1.S to use the alarm 1.
UT55A/UT52A
0: OFF (No function)
Alarm 1: 4353
Alarm 2: 4354
Alarm 3: 4355
Alarm 4: 4357
Alarm 5: 4358
Alarm 6: 4359
Alarm 7: 4361
Alarm 8: 4362
AUTO (ON ) / MAN (OFF) status: 4193
REM (ON) / LCL (OFF) status: 4194
STOP (ON) / RUN (OFF) status: 4195
Output tracking (ON) switching signal: 4201
UP55A
0: OFF (No function)
PV event-1:
4801
PV event-2
: 4802,
PV event-3
: 4803,
PV event 4: 4805,
PV event 5: 4806,
PV event 6 4807,
PV event 7: 4809,
PV event 8: 4810,
Time event 1: 4817,
Time event 2: 4818,
Time event 3: 4819,
Time event 4: 4821,
Time event 5: 4822,
Time event 6: 4823,
Time event 7: 4825,
Time event 8: 4826,
Time event 9: 4833,
Time event 10: 4834,
Time event 11: 4835,
Time event 12: 4837,
Time event 13: 4838,
Time event 14: 4839,
Time event 15: 4841,
Time event 16: 4842,
Alarm 1: 4353, Alarm 2: 4354,
Alarm 3: 4355, Alarm 4: 4357,
Alarm 5: 4358, Alarm 6: 4359,
Alarm 7: 4361, Alarm 8: 4362,
AUTO (ON ) / MAN (OFF) status: 4177,
Program RESET status: 4181,
Program RUN status: 4182,
Local operation status: 4183,
Remote operation status: 4185,
HOLD mode status: 4189,
Program advance status: 4187,
Pattern end signal (1 second): 4265,
Pattern end signal (3 seconds): 4266,
Pattern end signal (5 seconds): 4267,
Wait end signal (1 second) : 4257,
Wait end signal (3 seconds) : 4258,
Wait end signal (5 seconds) : 4259,
Output tracking (ON) switching signal: 4186
For the items other than below, see the Chapter 7
Functions and Applications of I Relays (for UT55A/UT52A/
UP55A).
D6202
AL2.S
AL2 function selection
D6203
AL3.S
AL3 function selection
D6204
OR.S
OUT relay function selection
D6205
OR2.S
OUT2 relay function selection