14-81
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT75A)
14
14.4 UT75A D Registers
Register
No.
Description
Range and meaning of value
D5115
A.LC
PV analog input low signal cutoff
0.0 to 5.0%
D5116 to D5120
D5121
IN_E1
PV2 input type
4
0: 0.4-2V (0.400 to 2.000 V)
41: 1-5V (1.000 to 5.000 V)
50: 0-2V (0.000 to 2.000 V)
51: 0-10V (0.00 to 10.00 V)
57: 0-125 (0.000 to 1.250 V)
D5122
UNIT_E1
PV2 input unit
Same as D5102
D5123
DP_E1
PV2
input decimal point position
Same as D5103
D5124
RH_E1
Maximum value of PV2 input range
Depends on the input type.
- For temperature input -
Set the temperature range that is actually controlled. (RL<RH)
- For voltage / current input -
Set the range of a voltage / current signal that is applied.
The scale across which the voltage / current signal is actually
controlled should be set using the maximum value of input
scale (SH) and minimum value of input scale (SL).
(Input is always 0% when RL = RH.)
D5125
RL_E1
Minimum value of PV2 input range
D5126
S
DP_E1
PV2
input scale decimal point position
Same as D5103
D5127
SH_E1
M
aximum value of PV2 input scale
Same as D5107, D5108
D5128
SL_E1
M
inimum value of PV2 input scale
D5129
BSL_E1
PV2 input burnout action
Same as D5109
D5130
RJC_E1
PV2 input reference junction
compensation
Same as D5110
D5131
ERJC_E1
PV2 input external RJC setpoint
-10.0 to 60.0°
C
D5132
RTD.S_E1
RTD wiring system
0: 3-W (3-wire system)
1: 4-W (4-wire system)
(The LL50A Parameter Setting Software is required to use
PV2 terminals input as PV.)
D5133
A.BS_E1
PV2 analog input bias
-
100.0 to 100.0% of PV2 input range span (EUS)
D5134
A.FL_E1
PV2 analog input filter
Same as D 5113
D5135
A.SR_E1
PV2
analog input square root extraction
Same as D5114
D5136
A.LC_E1
PV2 analog input low signal cutoff
Same as D5115
D5137 to D5140
D5141
IN_E2
AIN2 aux. analog input type
Same as D5121
D5142
UNIT_E2
AIN2 aux. analog input unit
Same as D5102
D5143
DP_E2
AIN2 aux. analog input decimal point position Same as D5103
D5144
RH_E2
Maximum value of AIN2 aux. analog input
range
Depends on the input type.
Set the range of a voltage signal that is applied.
The scale across which the voltage signal is actually controlled should
be set using the maximum value of input scale (SH) and minimum value
of input scale (SL).
(Input is always 0% when RL = RH.)
D5145
RL_E2
Minimum value of AIN2 aux. analog input
range
D5146
SDP_E2
AIN2 aux. analog input scale decimal point position Same as D5103
D5147
SH_E2
Maximum value of AIN2 aux. analog input scale
Same as D5107, D5108
D5148
S
L_E2
Minimum value of AIN2 aux. analog input scale
D5149
BSL_E2
AIN2 aux. analog input burnout action
Same as D5109
D5150 to D5151
D5152
A.BS_E2
AIN2 aux. analog input bias
-100.0 to 100.0% of AIN2 input range span (EUS)
D5153
A.FL_E2
AIN2 aux. analog input filter
Same as D5113
D5154
A.SR_E2
AIN2 aux. analog input square root extraction
Same as D5114
D5155
A.LC_E2
A
IN2 aux. analog input low signal cutoff
Same as D5115
D5156
D5157
DI6.D_E2
DI26 contact type
Same as D5137
D5158 to D5180