3-15
IM 05P07A01-01EN
Description of RS-485 Communication (for UT
Advanced with RS-485 Communication)
3
16 Writing to multiple D registers
Function
Data is written to D registers continuously for the specified number of registers from the
specified D register No.
• The maximum number of registers that can be written at a time is 50.
• For details on the response format at an error, see “
● Response in an error state
” in
“3.1.3 Configuration of Responses (response from UTAdvanced).”
• When data outside the setting range of parameters is set, the response is a normal
response, but the data is not written.
• Broadcasting can be specified. No response is returned when broadcasting is
specified.
Message (during normal operation)
Element
Message start
mark (:)
Address No.
(ADR)
Function code
(0x10)
Register
start No.
Number of
registers
Byte count
(Note 1)
Number of bytes in RTU mode
None
1
1
2
2
1
Number of bytes in ASCII
mode
1
2
2
4
4
2
Continuation of message
Write data
• • •
Write data
Error check
Message
end mark
(CR+LF)
2
• • •
2
2
None
4
• • •
4
2
2
Note 1: Byte count = 2 x number of write registers
Response (during normal operation)
Element
Message
start mark
(:)
Address No.
(ADR)
Function code
(0x10)
Register
start No.
Number of
registers
Error
check
Message
end mark
(CR+LF)
Number of bytes in RTU
mode
None
1
1
2
2
2
None
Number of bytes in ASCII
mode
1
2
2
4
4
2
2
3.1 Modbus Communication
Summary of Contents for UTAdvanced Series
Page 17: ...Blank Page...
Page 77: ...Blank Page...
Page 285: ...Blank Page...
Page 325: ...Blank Page...
Page 467: ...Blank Page...
Page 557: ...Blank Page...
Page 825: ...Blank Page...
Page 861: ...Blank Page...
Page 863: ...Blank Page...
Page 865: ...Blank Page...