9-23
IM 05P07A01-01EN
Functions and
Applications of I Relays (for UT35A/UT32A/UP35A)
9
Input (Status) Relay and Output (Status) Relay (5025 to 5280)
I relay No.
Symbol
Description
5025 to 5040
X_DI1 to X_DI2 *
DI1-DI2 status (Same as D7011) *
5041 to 5056
X_DI11 to X_DI15
DI11-DI15 status (Same as D7012)
5057 to 5072
5073 to 5088
5089 to 5104
X_DI41 to X_DI45
DI41-DI45 status (Same as D7015)
5105 to 5152
5153 to 5168
Y_AL1 to Y_AL3
AL1-AL3 status (Same as D7161)
5169 to 5184
Y_DO11 to
Y_DO15
DO11-DO15 status (Same sa D7162)
5185 to 5200
5201 to 5216
5217 to 5232
Y_DO41 to
Y_DO45
DO41-DO45 status (Same as D7165)
5233 to 5280
*: UP35A; X_DI1 to X_DI3 (DI1-DI3 status (Same as D7011)
Control (Status) Relay (5281 to 5408)
I relay No.
Symbol
Description
5281 to 5296
AL1_CTL to
AL3_CTL
Control AL1-AL3 status (Same as D7111)
5297 to 5312
DO11_CTL to
DO15_CTL
Control DO11-DO15 status (Same as D7112)
5313 to 5328
5329 to 5344
5345 to 5360
DO41_CTL to
DO45_CTL
Control DOI41-DO45 status (Same as D7115)
5361 to 5408
Special Relay (5409 to 5536)
I relay No.
Symbol
Description
5409 to 5424
TIM1 to TIM4
Time out flag (Same as D7221)
5425 to 5440
CNT1 to CNT4
Time out flag (Same as D7222)
5441
SMPCLK
Input sampling period (control period) clock
5442
CLK1
1-second clock
5443
CLK2
2-second clock
5444
CLK10
10-second clock
5445
CLK60
60-second clock
5447
CLK1P
1-second clock pulse
5448
CLK2P
2-second clock pulse
5449
CLK10P
10-second clock pulse
5450
CLK60P
60-second clock pulse
5457
PON
Power on flag
0: Power-on and initializing
1: During operation
5458
PLS1
Always ON
1: ON
5459
ZERO
Always OFF
0: OFF
5461
PDLVL
Power failure detection level
*1
0: Power failure of about 5
seconds or more
1: Power failure of about
less than 5 seconds
5473 to 5536
Free area
*1: No power failure is detected in the following cases, and the unit maintains normal operations.
▪ A momentary power failure of 20 ms or less in the case of 100 – 240 V AC
▪ A momentary power failure of 1 ms in the case of 24 V AC/DC
9.3 UT35A/UT32A/UT32A-D/UP35A/UP32A I Relays
Summary of Contents for UTAdvanced Series
Page 17: ...Blank Page...
Page 77: ...Blank Page...
Page 285: ...Blank Page...
Page 325: ...Blank Page...
Page 467: ...Blank Page...
Page 557: ...Blank Page...
Page 825: ...Blank Page...
Page 861: ...Blank Page...
Page 863: ...Blank Page...
Page 865: ...Blank Page...