D8001 48001
1F40
PTNO._C
R/W Program pattern number selection 0: Not select program pattern
1 to 30
D8002 48002
1F41
SEGNO._C
R/W Segment number designation
0
(1 to 99)
*:When reading from or writing to D8003 to
D8043 registers, write "0" to the register.
D8003 48003
1F42
SSP_L1
R/W Loop-1 Starting target setpoint
0.0 to 100.0% of PV input range (EU)
(Setting range: P.RL to P.RH)
D8004 48004
1F43
SSP_L2
R/W Loop-2 Starting target setpoint
D8005 48005
1F44
STC
R/W Start code
0: SSP (Program operation begins with the
starting target setpoint.
1: RAMP (Ramp-prioritized PV start)
2: TIME (Time-prioritized PV start)
4: LSP (Local-mode start)
5: RSP (Remote-mode start)
* STC=TIME cannot be selected when the
parameter SEG.T is TM.RT.
D8006 48006
1F45
WT.SW1
R/W Wait function ON/OFF 1
WT.SW1 to WT.SW5
0: OFF (Disable)
1: ON (Enable)
WZ.UP1 to WZ.UP5
0.0 to 10.0% of PV input range (EU)
WT.TM1 to WT.TM5
0: OFF (No function)
1 to 59999 (minute or second)
* Available only for the wait time at the segment
switching.
* Use the parameter TMU to set the time unit.
(Common in the instrument.)
D8007 48007
1F46
WZ.UP1
R/W
Upper-side wait zone 1
D8008 48008
1F47
WZ.LO1
R/W
Lower-side wait zone 1
D8009 48009
1F48
WT.TM1
R/W Wait time 1
D8010 48010
1F49
WT.SW2
R/W Wait function ON/OFF 2
D8011 48011
1F4A
WZ.UP2
R/W
Upper-side wait zone 2
D8012 48012 1F4B
WZ.LO2
R/W
Lower-side wait zone 2
D8013 48013 1F4C
WT.TM2
R/W Wait time 2
D8014 48014 1F4D
WT.SW3
R/W Wait function ON/OFF 3
D8015 48015 1F4E
WZ.UP3
R/W
Upper-side wait zone 3
D8016 48016 1F4F
WZ.LO3
R/W
Lower-side wait zone 3
D8017 48017
1F50
WT.TM3
R/W Wait time 3
D8018 48018
1F51
WT.SW4
R/W Wait function ON/OFF 4
D8019 48019
1F52
WZ.UP4
R/W
Upper-side wait zone 4
D8020 48020
1F53
WZ.LO4
R/W
Lower-side wait zone 4
D8021 48021
1F54
WT.TM4
R/W Wait time 4
D8022 48022
1F55
WT.SW5
R/W Wait function ON/OFF 5
D8023 48023
1F56
WZ.UP5
R/W
Upper-side wait zone 5
D8024 48024
1F57
WZ.LO5
R/W
Lower-side wait zone 5
D8025 48025
1F58
WT.TM5
R/W Wait time 5
D8026 48026
1F59
R.CYCL
R/W Number of repeat cycles
0 to 999, 1000: CONT (The controller indefinitely
repeats the segment specified by the RST and
REN parameters.)
D8027 48027 1F5A
R.STRT
R/W Repeat cycle start segment
number
1 to 99
1 ≤ R.STRT ≤ R.END ≤ 99
D8028 48028 1F5B
R.END
R/W Repeat cycle end segment number
D8029 48029 1F5C
D8030 48030 1F5D
D8031 48031 1F5E P.NAME
R/W Program pattern name
20-digit value of alphanumeric characters can be
set.
Arrangement:
D8031, D8032, D8033, D6004, D8035, D8036,
D8037, D8038, D8039, D8040, D8041
Write “0x00” to the register after the character
string.
D8032 48032 1F5F P.NAME
R/W Program pattern name
D8033 48033
1F60 P.NAME
R/W Program pattern name
D8034 48034
1F61 P.NAME
R/W Program pattern name
D8035 48035
1F62 P.NAME
R/W Program pattern name
D8036 48036
1F63 P.NAME
R/W Program pattern name
D8037 48037
1F64 P.NAME
R/W Program pattern name
D8038 48038
1F65 P.NAME
R/W Program pattern name
D8039 48039
1F66 P.NAME
R/W Program pattern name
D8040 48040
1F67 P.NAME
R/W Program pattern name
D8041 48041
1F68 P.NAME
R/W Program pattern name
D8042 48042
1F69 PTN.ERR
R
Read/write error information
0: Normal end
Except 0: error (See "Error information"
described later in this chapter.)
D8043 to D8100
Summary of Contents for UTAdvanced Series
Page 17: ...Blank Page...
Page 77: ...Blank Page...
Page 285: ...Blank Page...
Page 325: ...Blank Page...
Page 467: ...Blank Page...
Page 557: ...Blank Page...
Page 825: ...Blank Page...
Page 861: ...Blank Page...
Page 863: ...Blank Page...
Page 865: ...Blank Page...