8-107
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT35A/UT32A/UT32A-D/UP35A/UP32A)
8
8.4 UT35A/UT32A/UT32A-D/UP35A/UP32A D Registers
8.4.8 Program Pattern for UP35A/UP32A (D8001 to D9000)
Pattern Data Setting (D8001 to D8100)
Register
No.
Ref.
No.
H No.
Register
symbol
R/W
Description
Range and meaning of value
D8001 48001
1F40
PTNO._C
R/W Program pattern number selection 0: Not select program pattern
1 to 2 (4 when the option “/AP” is specified.)
D8002 48002
1F41
SEGNO._C
R/W Segment number designation
0
(1 to 20. (40 when the option “/AP” is specified.))
* When reading from or writing to D8003 to
D8043 registers, write "0" to the register.
D8003 48003
1F42
SSP_L1
R/W Starting target setpoint
0.0 to 100.0% of PV input range (EU)
(Setting range: P.RL to P.RH)
D8004 48004
1F43
D8005 48005
1F44
STC
R/W Start code
0: SSP (Program operation begins with the
starting target setpoint.
1: RAMP (Ramp-prioritized PV start)
2: TIME (Time-prioritized PV start)
3: LSP (Local-mode start)
* STC=TIME cannot be selected when the
parameter SEG.T is TM.RT.
D8006 48006
1F45
WT.SW1
R/W Wait function ON/OFF
0: OFF (Disable)
1: ON (Enable)
D8007 48007
1F46
WZ.UP1
R/W
Upper-side wait zone
0.0 to 10.0% of PV input range (EU)
D8008 48008
1F47
WZ.LO1
R/W
Lower-side wait zone
OFF: No function
0.00 to 999.59 (“hour.minute” or “minute.
D8009 48009
1F48
WT.TM1
R/W Wait time
0: OFF (No function)
1 to 59999 (minute or second)
* Available only for the wait time at the segment
switching.
* Use the parameter TMU to set the time unit.
(Common in the instrument.)
D8010 to D8025
D8026 48026
1F59
R.CYCL
R/W Number of repeat cycles
0 to 999, 1000: CONT (The controller indefinitely
repeats the segment specified by the RST and
REN parameters.)
D8027 48027 1F5A
R.STRT
R/W Repeat cycle start segment
number
1 to 20 (40 when the option “/AP” is specified.)
1 ≤ R.STRT ≤ R.END ≤ 20 (40)
D8028 48028 1F5B
R.END
R/W Repeat cycle end segment number
D8029 to D8030
D8031 48031 1F5E P.NAME
R/W Program pattern name
20-digit value of alphanumeric characters can be
set.
Arrangement:
D8031, D8032, D8033, D6004, D8035, D8036,
D8037, D8038, D8039, D8040, D8041
Write “0x00” to the register after the character
string.
D8032 48032 1F5F P.NAME
R/W Program pattern name
D8033 48033
1F60 P.NAME
R/W Program pattern name
D8034 48034
1F61 P.NAME
R/W Program pattern name
D8035 48035
1F62 P.NAME
R/W Program pattern name
D8036 48036
1F63 P.NAME
R/W Program pattern name
D8037 48037
1F64 P.NAME
R/W Program pattern name
D8038 48038
1F65 P.NAME
R/W Program pattern name
D8039 48039
1F66 P.NAME
R/W Program pattern name
D8040 48040
1F67 P.NAME
R/W Program pattern name
D8041 48041
1F68 P.NAME
R/W Program pattern name
D8042 48042
1F69 PTN.ERR
R
Read/write error information
0: normal end
Except 0: error (See "Error information"
described later in this chapter.)
D8043 to D8100