8-46
IM 05P07A01-01EN
8.4 UT35A/UT32A/UT32A-D/UP35A/UP32A D Registers
Loop-2 SP and Alarm Setpoint Setting of Groups 1 to 4 (D3601 to D3700)
Register
No.
Description
Range and meaning of value
D3501
SP_L2_1
Target setpoint of group 1
0.0 to 100.0% of PV input range (EU) (Setting
range: SPL to SPH)
D3502
SUB_1
Sub-target setpoint (in Two-position
two-level control) of group 1
Set the offset from SP.
-100.0 to 100.0% of PV input range span (EUS)
D3503
PIDN_L2_1
PID number selection of group 1
Set a PID group number to use.
1 to 4 (Depends on the PIDG. setting.)
D3504
A1_L2_1
Alarm-1 setpoint of group 1
Set a display value of setpoint of PV alarm, SP
alarm, deviation alarm, output alarm, or velocity
alarm.
-19999 to 30000 (Set a value within the input
range.)
Decimal point position depends on the input type.
D3505
A2_L2_1
Alarm-2 setpoint of group 1
D3506
A3_L2_1
Alarm-3 setpoint of group 1
D3507
A4_L2_1
Alarm-4 setpoint of group 1
D3508 to D3520
D3521 to
D3527
SP_L2_2 to A4_L2_2
Target setpoint of group 2 to Alarm-4
setpoint of group 2
Same as 2501 to D2507
D3528 to D3540
D3541 to
D3547
SP_L2_3 to A4_L2_3
Target setpoint of group 2 to Alarm-4
setpoint of group 2
Same as D2501 to D2507
D3548 to D3560
D3561 to
D3567
SP_L2_4 to A4_L2_4
Target setpoint of group 2 to Alarm-4
setpoint of group 2
Same as D2501 to D2507
D3568 to D3700
Loop-2 SP-related Setting (D3801 to D3900)
Register
No.
Description
Range and meaning of value
D3701 to D3702
D3703
RT_L2
Remote input ratio
SP = Remote input x RT + Remote input bias
0.001 to 9.999
D3704
RBS_L2
Remote input bias
-100.0 to 100.0% of PV input range span (EUS)
D3705
UPR_L2
SP ramp-up rate
Used to prevent SP from changing suddenly.
Set a ramp-up rate or ramp-down rate per hour or
minute. Set a time unit using the parameter TMU.
0: OFF (Disable)
0.0 + 1 digit to 100.0% of PV input range span (EUS)
D3706
DNR_L2
SP ramp-down rate
D3707
TMU_L2
SP ramp-rate time unit
0: HOUR (Ramp-up rate or ramp-down rate per hour)
1: MIN (Ramp-up rate or ramp-down rate per minute)
D3708 to D3709
D3710
SPT_L2
SP tracking selection
Tracking is performed when the mode changes
from Remote to Local. (The local setpoint keeps
track of the remote setpoint.)
0: OFF (Disable)
1: ON (Enable)
D3711
PVT_L2
PV tracking selection
Causes the setpoint to keep track of the PV so the
setpoint automatically reverts to its original value at
a preset rate of change. The UPR, DNR, and TMU
are used in combination.
Operating conditions:
1
) MAN → AUTO, 2) STOP → AUTO,
3) Power-on, 4) SP number change,
5) SP change
0: OFF (Disable)
1: ON (Enable)
D3712
S.TM
Starting time of program operation
0 to 59999 (minute or second)
* Use the parameter TMU to set the time unit.
D3713
PNC
Program pattern number clearance
0: OFF (Not cleared)
1: ON (Cleared. (Set the program No.) before
restart program operation)
* The controller resets (clears) the program pattern
number on the operating display to “0” at the
end of program operation.
D3712 to D3800