IM 05P07A01-01EN
14.4 UT75A D Registers
Loop-2 SP-related Setting (D3801 to D3900)
Register
No.
Description
Range and meaning of value
D3801
RMS_L2
Remote input method
0: RSP (Via remote (aux. analog) input)
1: COM (Via communication)
RSP is not displayed if the remote (auxiliary analog)
input is not specified.
COM is not displayed if the communication function
is not specified.
When neither the remote (auxiliary analog) input
nor communication function is specified, this
parameter is not displayed.
D3802
RFL_L2
R
emote input filter
0: OFF (Disable)
1 to 120 s
D3803
RT_L2
Remote input ratio
SP = Remote input x RT + Remote input bias
0.001 to 9.999
D3804
RBS_L2
Remote input bias
-
100.0 to 100.0% of PV input range span (EUS)
D3805 to D3806
D3807
TMU_L2
SP ramp-rate time unit
0: HOUR (Ramp-up rate or ramp-down rate per
hour)
1: MIN (Ramp-up rate or ramp-down rate per
minute)
D3808 to D3809
D3810
SPT_L2
SP tracking selection
Tracking is performed when the mode changes
from Remote to Local. (The local setpoint keeps
track of the remote setpoint.)
0: OFF (Disable)
1: ON (Enable)
D3811
PVT_L2
P
V tracking selection
C
auses the setpoint to keep track of the PV so the
setpoint automatically reverts to its original value at
a preset rate of change. The UPR, DNR, and TMU
are used in combination.
Operating conditions:
1) M
AN → AUTO, 2) STOP → AUTO,
3) Power-on, 4) SP number change,
5) SP change
0: OFF (Disable)
1: ON (Enable)
D3812 to D3900