6-134
IM 05P07A01-01EN
6.4 UT55A/UT52A/UP55A D Registers
Register
No.
Ref.
No.
H No.
Register
symbol
R/W
Description
Range and meaning of value
D8109 48109 1FAC
PV.TY1
R/W
PV event-1 type
OFF: Disable
(Energized)
1: PV high limit, 02: PV low limit,
3: SP high limit, 04: SP low limit,
5: Deviation high limit,
6: Deviation low limit,
7: Deviation high and low limits,
8: Deviation within high and low limits,
9: Target SP high limit,
10: Target SP low limit,
11: Target SP deviation high limit,
12: Target SP deviation low limit,
13: Target SP deviation high and low limits,
14: Target SP deviation within high and low
limits,
15: OUT high limit,
16: OUT low limit,
17: Cooling-side OUT high limit,
18: Cooling-side OUT low limit
* Add 100 for "de-energized". For example, when
the PV high limit is de-energized, the setting
is 101.
D8110 48110 1FAD
PV.EV1
R/W
PV event-1 setpoint
Set a display value of setpoint of PV alarm, SP
alarm, deviation alarm, or output alarm.
-19999 to 30000 (Set a value within the input
range.)
Decimal point position depends on the input
type.
D8111
48111 1FAE
PV.TY2
R/W
PV event-2 type
PV.TY2 to PV.TY8
Same as D8109
PV.EV2 to PV.EV8
Same as D8110
D8112 48112 1FAF
PV.EV2
R/W
PV event-2 setpoint
D8113 48113 1FB0
PV.TY3
R/W
PV event-3 type
D8114 48114 1FB1
PV.EV3
R/W
PV event-3 setpoint
D8115 48115 1FB2
PV.TY4
R/W
PV event-4 type
D8116 48116 1FB3
PV.EV4
R/W
PV event-4 setpoint
D8117 48117 1FB4
PV.TY5
R/W
PV event-5 type
D8118 48118 1FB5
PV.EV5
R/W
PV event-5 setpoint
D8119 48119 1FB6
PV.TY6
R/W
PV event-6 type
D8120 48120 1FB7
PV.EV6
R/W
PV event-6 setpoint
D8121 48121 1FB8
PV.TY7
R/W
PV event-7 type
D8122 48122 1FB9
PV.EV7
R/W
PV event-7 setpoint
D8123 48123 1FBA
PV.TY8
R/W
PV event-8 type
D8124 48124 1FBB
PV.EV8
R/W
PV event-8 setpoint
D8125 48125 1FBC
TME1
R/W Start condition of time event 1
0: OFF (Start OFF state)
1: ON (Start ON state)
D8126 48126 1FBD
T.ON1
R/W On time of time event 1
0: Unregistered
1 to 59999 (minute or second)
* Available only within the segment time.
* OFF when the operation mode is changed to
the mode except the program operation.
* Use the parameter TMU to set the time unit.
(Common in the instrument.)
D8127 48127 1FBE
T.OF1
R/W
Off time of time event 1