8-74
IM 05P07A01-01EN
8.4 UT35A/UT32A/UT32A-D/UP35A/UP32A D Registers
Heater Break Alarm Setting (D5401 to D5500)
Register
No.
Description
Range and meaning of value
D5401
HB1.S
Heater break alarm-1 function
selection
0: Heater current measurement
1: Heater break alarm (Heating-side)
2: Cooling-side heater break alarm
D5402
HB2.S
Heater break alarm-2 function
selection
D5403
HB1
Heater break alarm-1 current
setpoint
0: OFF
0.1 to 300.0 Arms
D5404
HB2
Heater break alarm-2 current
setpoint
D5405
CT1.T
CT1 coil winding number ratio
1 to 3300
D5406
CT2.T
CT2 coil winding number ratio
D5407
HDN1
Heater break alarm-1 On-delay
timer
0 to 5999 (second)
D5408
HDN2
Heater break alarm-2 On-delay
timer
D5409
HDF1
Heater break alarm-1 Off-delay
timer
0 to 5999 (second)
D5410
HDF2
Heater break alarm-2 Off-delay
timer
D5411
HB1.D
Heater break alarm-1 contact type
0: CLS (When the event occurs, the contact is closed.)
1: OPN (When the event occurs, the contact is opened.)
D5412
HB2.D
Heater break alarm-2 contact type
D5413 to D5500