8-14
IM 05P07A01-01EN
8.4 UT35A/UT32A/UT32A-D/UP35A/UP32A D Registers
Bit Configuration of D2040: TIME_EV_1 (Time event status 1)
Bit
Symbol
Event
0
TIME_EV1
0: Time event is OFF
1: Time event is ON
1
TIME_EV2
2
TIME_EV3
3
4
TIME_EV4
0: Time event is OFF
1: Time event is ON
5 to 15
D2044 to D2049
Register
No.
Description
Range and meaning of value
D2044
SEG_USE
Number of segments contained in the selected
pattern
0 to 20 (40 when the option “/AP” is specified.)
D2045
NOW_RCY
Number of repetitions of the pattern in operation
0 to 999
D2046
REM_RCY
Number of repetitions of the pattern in operation
0 to 999
D2047
ALL_RCY
Remaining number of repetitions of the pattern in
operation
0 to 1000
D2048
NOW_RST
Repeat Start number of the current segment
1 to 20 (40 when the option “/AP” is specified.)
D2049
NOW_REN
Repeat End number of the current segment
1 to 20 (40 when the option “/AP” is specified.)
Bit Configuration of D2050: PV_EV_OUT (PV event output status)
0
PV_EV1_OUT
0: PV event output is OFF
1: PV event output is ON
1
PV_EV2_OUT
2 to 15
D2061, D2062
Register
No.
Description
Range and meaning of value
D2061
HC1
Heter break alarm-1 current value
display
0.0 to 360.0 Arms
D2062
HC2
Heter break alarm-2 current value
display
0.0 to 360.0 Arms
Bit Configuration of D2063: CT_AL (Heater break alarm status)
Bit
Symbol
Event
0
CT_AL1
‘1’ when heter break alarm-1 is ON; ‘0’ when OFF
1
CT_AL2
‘1’ when heter break alarm-2 is ON; ‘0’ when OFF
2 to 15
Bit Configuration of D2064: VALV (Valve status)
Bit
Symbol
Event
0
VALV_GUSS
0: Operation by feedback input
1: Operation by estimating type
1
VALV_OPEN
0: Output off, 1: Output on
2
VALV_CLOSE
0: Output off, 1: Output on
3
VALV_AT
0: Stop automatic valve position adjustment
1: Automatic valve position adjustment
4 to 15
Bit Configuration of D2065:
AD2.E
(A/D converter error status 2)
Bit
Symbol
Event
0
VALVBO
Feedback input resistor/current burnout
1
VALV_ATERR
Valve position automatic adjustment error
2 to 15