6-109
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT55A/UT52A/UP55A)
6
6.4 UT55A/UT52A/UP55A D Registers
System Setting (D6401 to D6500)
Register
No.
Description
Range and meaning of value
D6401
R.MD
Restart mode
Set how the controller should recover from a power failure
of 5 seconds or more.
UT55A/UT52A
0: CONT (Continue action set before power failure.)
1: MAN (Start from MAN.)
2: AUTO (Start from AUTO.)
UP55A
0: CONT (Continue action set before power failure.)
1: MAN (Start from MAN.)
2: RESET (Start from AUTO and RESET. The preset
output value is outputted.)
D6402
R.TM
Restart timer
Set time between power on and the instant where
controller starts computation.
0 to 10 s
D6403 to D6407
D6408
EPO
Input error preset output
Set preset output value when the input burnout or ADC
error occurs. Manual output is prioritized when input
burnout occurs in MAN.
0: Preset output
1: 0% output
2: 100% output
D6409
C.GRN
Response as GREEN Series
0: OFF (Works as UT55A/UT52A/UP55A in communication
of device information response or broadcasting.)
1: ON (Works as GREEN Series in communication of
device information response or broadcasting.)
D6410
FREQ
Power frequency
0: AUTO
1: 60 Hz
2: 50 Hz
D6411 to D6416
D6417
QSM
Quick setting mode
0: OFF (Disable)
1: ON (Enable)
D6418
LANG
Guide display language
0: ENG (English)
1: FRA (French)
2: GER (German)
3: SPA (Spanish)
D6419 to D6420
D6421
U.DEF
Initialization to user default value
1
2345: Initialization, automatically returned to "0" after
initialization.
D6422
D6423
F.DEF
Initialization to factory default value
-
12345: Initialization, automatically returned to "0" after
initialization. *
D6424
D6425
P.DEF
Clearing all program pattern data
13579: Initialization, automatically returned to "0" after
initialization.
* Data all deletions in menu [PROG]
D6426 to D6430
D6431
LEVL
Parameter display level
1: EASY (Easy setting mode)
2: STD (Standard setting mode)
3: PRO (Professional setting mode)
D6432 to D6500
*: UP55A does not respond for the initialization command via Ethernet communication.
Free Area (D6501 to D7000)
Register
No.
Description
Range and meaning of value
D6501 to D7000
Free area
Summary of Contents for UTAdvanced Series
Page 17: ...Blank Page...
Page 77: ...Blank Page...
Page 285: ...Blank Page...
Page 325: ...Blank Page...
Page 467: ...Blank Page...
Page 557: ...Blank Page...
Page 825: ...Blank Page...
Page 861: ...Blank Page...
Page 863: ...Blank Page...
Page 865: ...Blank Page...