Local-mode Operation Setting for UP55A (D2201 to D2300)
Register
No.
Description
Range and meaning of value
D2201
LSP_L1
Loop-1 local target setpoint
0.0 to 100.0% of PV input range (EU) (Setting
range: P.RL to P.RH)
D2202
LSP_L2
Loop-2 local target setpoint
D2203
L.PID
PID number selection for local-mode operation
Set a PID group number to use.
1 to 8
* Available only for the L.PID when ZON = 0 or 5.
* If set to “Local PID selection,” local PID is
selected irrespective of the operation modes.
D2204
L.TY1
Local event-1 type
OFF: Disable
(Energized)
01: PV high limit, 02: PV low limit,
03: SP high limit, 04: SP low limit,
05: Deviation high limit,
06: Deviation low limit,
07: Deviation high and low limits,
08: Deviation within high and low limits,
09: Target SP high limit,
10: Target SP low limit,
11: Target SP deviation high limit,
12: Target SP deviation low limit,
13: Target SP deviation high and low limits,
14: Target SP deviation within high and low limits,
15: OUT high limit, 16: OUT low limit,
17: Cooling-side OUT high limit,
18: Cooling-side OUT low limit
* Add 100 for "de-energized". For example, when
the PV high limit is de-energized, the setting is
101.
D2205
L.EV1
Local event-1 setpoint
Set a display value of setpoint of PV alarm, SP
alarm, deviation alarm, or output alarm.
-19999 to 30000 (Set a value within the input
range.)
Decimal point position depends on the input type
D2206
L.TY2
Local event-2 type
Same as D2204
D2207
L.EV2
Local event-2 setpoint
Same as D2205
D2208
L.TY3
Local event-3 type
Same as D2204
D2209
L.EV3
Local event-3 setpoint
Same as D2205
D2210
L.TY4
Local event-4 type
Same as D2204
D2211
L.EV4
Local event-4 setpoint
Same as D2205
D2212
L.TY5
Local event-5 type
Same as D2204
D2213
L.EV5
Local event-5 setpoint
Same as D2205
D2214
L.TY6
Local event-6 type
Same as D2204
D2215
L.EV6
Local event-6 setpoint
Same as D2205
D2216
L.TY7
Local event-7 type
Same as D2204
D2217
L.EV7
Local event-7 setpoint
Same as D2205
D2218
L.TY8
Local event-8 type
Same as D2204
D2219
L.EV8
Local event-8 setpoint
Same as D2205
D2220 to D2300
Summary of Contents for UTAdvanced Series