14-123
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT75A)
14
14.4 UT75A D Registers
Program Pattern Setting (D7701 to D7900)
Register
No.
Description
Range and meaning of value
D7701
SSP_L1
Loop-1 Starting target setpoint
0.0 to 100.0% of PV input range (EU)
(Setting range: P.RL to P.RH)
D7702
SSP_L2
Loop-2 Starting target setpoint
D7703
STC
Start code
0: SSP (Program operation begins with the starting target
setpoint.
1: RAMP (Ramp-prioritized PV start)
2: TIME (Time-prioritized PV start)
D7704
WT.SW1
Loop-1 Wait function ON/OFF
WT.SW_L1, WT.SW_L2
0: OFF (Disable)
1: ON (Enable)
WZ.UP_L1, WZ.UP_L2
WZ.LO_L1, WZ.LO_L2
0.0 to 10.0% of PV input range (EU)
* Available only for the wait time at the segment switching.
* Use the parameter TMU to set the time unit. (Common in
the instrument.)
D7705
WZ.UP1
Loop-1 Upper-side wait zone
D7706
WZ.LO1
Loop-1 Lower-side wait zone
D7707
WT.SW2
Loop-2 Wait function ON/OFF
D7708
WZ.UP2
Loop-2 Upper-side wait zone
D7709
WZ.LO2
Loop-2 Lower-side wait zone
D7710
R.CYCL
Number of repeat cycles
0 to 999, CONT (limitless number of times)
D7711 to D7799
D7800
JC
Junction code
CONT: Switching for continuation
HOLD: Hold-on switching (the controller holds the end-
of segment setpoint when the segment is completed, to
perform control).
D7801
TSP_L1_1
Loop-1, segment-1 final target
setpoint
0.0 to 100.0% of PV input range (EU) (Setting range: P.RL
to P.RH)
D7802
TSP_L2_1
Loop-2, segment-1 final target
setpoint
D7803
TIME_1
Segment time setting of segment 1
-: Unregistered
0.00 to 99.59 (“hour.minute” or “minute.second”)
* Use the parameter TMU to set the time unit. (Common in
the instrument.)
* If the setting is 0.00, TSP changes in stepwise after one
control period.
D7804
S.PID_L1_1
Loop-1, segment-1 segment PID
number selection
1 to 16
*However, parameter ZON is set to 0.
D7805
S.PID_L2_1
Loop-2, segment-1 segment PID
number selection
D7806 to
D7810
TSP_L1_2 to
S.PID_L2_2
Loop-1, segment-2 final target
setpoint to Loop-2, segment-2
segment PID number selection
Same as D7801 to D7805.
D7806 to
D7810
TSP_L1_3 to
S.PID_L2_3
Loop-1, segment-3 final target
setpoint to Loop-2, segment-3
segment PID number selection
Same as D7801 to D7805.
D7806 to
D7810
TSP_L1_4 to
S.PID_L2_4
Loop-1, segment-4 final target
setpoint to Loop-2, segment-4
segment PID number selection
Same as D7801 to D7805.
D7806 to
D7810
TSP_L1_5 to
S.PID_L2_5
Loop-1, segment-5 final target
setpoint to Loop-2, segment-5
segment PID number selection
Same as D7801 to D7805.
D7806 to
D7810
TSP_L1_6 to
S.PID_L2_6
Loop-1, segment-6 final target
setpoint to Loop-2, segment-6
segment PID number selection
Same as D7801 to D7805.
D7806 to
D7810
TSP_L1_7 to
S.PID_L2_7
Loop-1, segment-7 final target
setpoint to Loop-2, segment-7
segment PID number selection
Same as D7801 to D7805.