6-88
IM 05P07A01-01EN
6.4 UT55A/UT52A/UP55A D Registers
Output Setting (D5301 to D5400)
Register
No.
Description
Range and meaning of value
D5301
OT.H
Heating-side control output selection
0: OFF
1: OUT terminals (voltage pulse)
2: OUT terminals (current)
3: OUT terminals (relay)
4: OUT2 terminals (voltage pulse)
5: OUT2 terminals (current)
6: OUT2 terminals (relay)
When the UTAdvanced parameter is set by key stroke,
the heating-side control output selection, and cooling-side
control output selection comprise one parameter.
D5302
OT.C
Cooling-side control output selection
D5303
CT
Control output cycle time
Heating-side control output cycle
time (in Heating/cooling control)
0.5 to 1000.0 s
D5304
CTc
Cooling-side control output cycle
time
D5305 to D5310
D5311
V.AT
Automatic valve position adjustment
0: O
FF (Stop automatic adjustment)
1: O
N (Start automatic adjustment)
D5312
V.RS
Valve position setting reset
0: OFF
1
: ON (Resets the valve adjustment settings and causes
the indication “V.RS” to blink.)
D5313
V.L
Fully-closed valve position setting
Pressing the SET/ENTER key with valve position set
to the fully-closed position by Down arrow key causes
the adjusted value to be stored. When V.L adjustment is
complete, V.L stops blinking.
D5314
V.H
Fully-opened valve position setting
Pressing the SET/ENTER key with valve position set to
the fully-opened position by Up arrow key causes the
adjusted value to be stored. When V.H adjustment is
complete, V.H stops blinking.
D5315
TR.T
Valve traveling time
5 to 300 s
D5316
V.MOD
Valve adjusting mode
0:
V
alve position feedback type
1:
V
alve position feedback type (moves to the estimating
type if a feedback input error or break occurs.)
2:
V
alve position estimating type
D5317 to D5320
D5321
RTS
Retransmission output type of RET
0: OFF (Disable)
1: P
V1 (PV)
2: SP1 (SP)
3: O
UT1 (OUT (Valve opening: 0 to 100 % in Position
proportional control))
4: L
PS (15 V DC loop power supply)
5: P
V2 (Loop-2 PV)
6: SP2 (Loop-2 SP)
7: OUT2 (Loop-2 OUT)
8: TSP1 (Target SP)
9: HOUT1 (Heating-side OUT)
10: COUT1 (Cooling-side OUT)
11: MV1 (Position proportional output (internal computed
value))
12: TSP2 (Loop-2 target SP)
13: HOUT2 (Loop-2 heating-side OUT)
14: COUT2 Loop-2 cooling-side OUT
15: MV2 (Loop-2 position proportional output (internal
computed value))
16: PV (PV terminals analog input)
17: RSP (RSP terminals analog input)
18: AIN2 (AIN2 terminals analog input)
19: ANI4 (AIN4 terminals analog input)
Loop-2 setting values are unavailable in Single-loop
control.