1-1
IM 05P07A01-01EN
Overview
1
1.1 UTAdvanced Communication
The UTAdvanced communication supports RS-485 communication and Ethernet
communication.
Three types of RS-485 communication are provided.
Host communication: Modbus communication, PC link communication, and ladder
communication that enable centralized monitoring of the UTAdvanced by a host
computer.
Coordinated operation: A system of coordinated operation is configured with a master
controller and a number of slave controllers, all of which are UTAdvanced. The slave
controllers are set to operate in the same way as the master controller.
Peer-to-peer communication: Enables sharing of data with other UTAdvanced by reading
and writing peer-to-peer communication registers in the ladder program.
The UTAdvanced with Ethernet communication can be connected to IEEE802.3-
compliant network (10BASE-T/100BASETX). A serial gateway function can increase the
number of connected controllers.
► Peer-to-peer communication: LL50A Parameter Setting Software User's Manual
Communication
function
Protocol
Connectable device
Terminal position
Suffix code
Remarks
RS-485
communi-
cation
RS-485 host
communication
Modbus/RTU
Modbus/ASCII
PC
Touch panel
PCL (sequencer)
The slave devices for
Ethernet communication:
UT75A/UT55A/UT35A/
UP55A/UP35A/UP32A
UT75A/UT55A/UP55A:
Rear terminals
(E3 and E4-terminal areas)
UT52A/UT32A/UT32A-D/
UP32A: Rear terminals
(E1-terminal area)
UT35A/UP35A: Rear
terminals
(E3-terminal area)
UM33A: Rear terminals
(E1-terminal area)
UT75A/UT55A:
Type 3 = 1,
Type 2 = 1 or 2
UP55A:
Type 3 = 1,
Type 2 = 2
UT52A/UT32A/
UT32A-D/UP32A/
UM33A:
Type 2 = 1
UT35A/UP35A:
Type 3 = 1
–
PC link
PC link
(with checksum)
–
Ladder
PCL (sequencer)
–
Coordinated
operation
Coordinated
operation
UTAdvanced
GREEN Series * (All
models except for
UM350/UM330/UM351/
UM331)
–
Peer-to-peer
communication
Peer-to-peer
communication
UTAdvanced
(All models except for
UM33A)
Configure the
ladder sequence
function using
LL50A (sold
separately)
Ethernet
communication
Modbus/TCP
PC
Touch panel
PCL (sequencer)
Rear Ethernet terminal
(E3-terminal area)
UT75A/UT55A/
UT35A/UP55A/
UP35A:
Type 3 = 2
–
*: GREEN Series controllers are the digital indicating controllers of YOKOGAWA.
► Terminal position: UTAdvanced Operation Guide or User’s Manual
Chapter 1 Overview
Summary of Contents for UTAdvanced Series
Page 17: ...Blank Page...
Page 77: ...Blank Page...
Page 285: ...Blank Page...
Page 325: ...Blank Page...
Page 467: ...Blank Page...
Page 557: ...Blank Page...
Page 825: ...Blank Page...
Page 861: ...Blank Page...
Page 863: ...Blank Page...
Page 865: ...Blank Page...