
14-39
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT75A)
14
14.4 UT75A D Registers
Register
No.
Description
Range and meaning of value
D3551
RP1_L1
Reference point 1
Set reference points at which switching is carried
out between groups
of PID constants according to the given temperature
zone.
0.0 to 100.0% of PV input range (EU)
(RP1 ≤ RP2 ≤ RP3 ≤ RP4 ≤ RP5 ≤ RP6 ≤ RP7)
D3552
RP2_L1
Reference point 2
D3553
RP3_L1
Reference point 3
D3554
RP4_L1
Reference point 4
D3555
RP5_L1
Reference point 5
D3556
RP6_L1
Reference point 6
D3557
RP7_L1
Reference point 7
D3558
RHY_L1
Zone PID switching hysteresis
Hysteresis can be set for switching at a reference
point.
0.0 to 10.0% of PV input range span (EUS)
D3559
RDV_L1
Reference deviation
Set a deviation from SP. The PID for reference
deviation is used if there is a larger deviation than
the preset reference deviation.
0: OFF (Disable)
0.0 + 1 digit to 100.0% of PV input range span (EUS)
D3560 to D3600
Summary of Contents for UTAdvanced Series
Page 17: ...Blank Page...
Page 77: ...Blank Page...
Page 285: ...Blank Page...
Page 325: ...Blank Page...
Page 467: ...Blank Page...
Page 557: ...Blank Page...
Page 825: ...Blank Page...
Page 861: ...Blank Page...
Page 863: ...Blank Page...
Page 865: ...Blank Page...