12-17
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT35A-L)
12
12.4 UT35A-L D Registers
Register
No.
Description
Range and meaning of value
D2841
HY1_L1
Alarm-1 hysteresis
Set a display value of setpoint of hysteresis.
-19999 to 30000 (Set a value within the input
range.)
Decimal point position depends on the input type.
D2842
HY2_L1
Alarm-2 hysteresis
D2843
HY3_L1
Alarm-3 hysteresis
D2844 to D2848
D2849
DYN1_L1
Alarm-1 On-delay timer
An alarm output is ON when the delay timer expires
after the alarm setpoint is reached.
0 to 5999 (second)
D2850
DYN2_L1
Alarm-2 On-delay timer
D2851
DYN3_L1
Alarm-3 On-delay timer
D2852 to D2856
D2857
DYF1_L1
Alarm-1 Off-delay timer
An alarm output is OFF when the delay timer
expires after the alarm setpoint is reached.
0 to 5999 (second)
D2858
DYF2_L1
Alarm-2 Off-delay timer
D2859
DYF3_L1
Alarm-3 Off-delay timer
D2860 to D2900
PV-related Setting (D2901 to D3000)
Register
No.
Description
Range and meaning of value
D2901
BS_L1
PV input bias
-100.0 to 100.0% of PV input range span (EUS)
D2902
FL_L1
PV input filter
0: OFF (Disable)
1 to 120 s
D2903 to D2910
D2911
HYS_L1
Limit control output hysteresis
0.0 to 100.0% of PV input span
(EUS)
D2912 to D3000
Free Area (D3001 to D5000)
Register
No.
Description
Range and meaning of value
D3001 to D5000
Free area