10-40
IM 05P07A01-01EN
10.4 UM33A D Registers
Register
No.
Description
Range and meaning of value
D6061
MSG4
Message-4 *2
20-digit value of alphanumeric characters can be
set.
Arrangement:
D6061, D6062, D6063, D6064, D6065, D6066,
D6067, D6068, D6069, D6070, D6071
Write “0x00” to the register after the character
string.
D6062
MSG4
D6063
MSG4
D6064
MSG4
D6065
MSG4
D6066
MSG4
D6067
MSG4
D6068
MSG4
D6069
MSG4
D6070
MSG4
D6071
MSG4
D6072 to D6100
D6101
DI1.D
DI1 contact type
0: The assigned function is enabled when the
contact is closed.
1: The assigned function is enabled when the
contact is opened.
D6102
DI2.D
DI2 contact type
D6102 to D6200
*1: Same parameter exists in other menu. “-D” is added to the end of the parameter in DI.SL menu.
*2: With regards to the information on D6001 to D6011, D6021 to D6031, D6041 to D6051, and
D6061 to D6071, 11 D registers comprise one message.
DO Function Setting (D6201 to D6300)
Register
No.
Description
Range and meaning of value
D6201 to D6210
D6211
AL1.S
AL1 function selection
Set an I relay number (Setting range: 4001 to 6304).
Ex.) Set the number 4353 for AL1.S to use the alarm 1.
0: OFF (No function)
Alarm 1: 4353
Alarm 2: 4354
Alarm 3: 4355
Alarm 4: 4357
Alarm 5: 4358
Alarm 6: 4359
Alarm 7: 4361
Alarm 8: 4362
FAIL (Normally ON) output: 4256
For the items other than below, see the Chapter 11
Functions and Applications of I Relays (for UM33A).
D6212
AL2.S
AL2 function selection
D6213
AL3.S
AL3 function selection
D6214
AL4.S
AL4 function selection
D6215
AL1.D
AL1 contact type
0: When the event of assigned function occurs, the
contact is closed.
1: When the event of assigned function occurs, the
contact is opened.
D6216
AL2.D
AL2 contact type
D6217
AL3.D
AL3 contact type
D6218
AL4.D
AL4 contact type
D6219 to D6220
D6221
DO1.S_E1
DO11 function selection
Same as D6211
D6222
DO2.S_E1
DO12 function selection
D6223
DO3.S_E1
DO13 function selection
D6224
DO4.S_E1
DO14 function selection
D6225
DO5.S_E1
DO15 function selection
D6226
DO1.D_E1
DO11 contact type
Same as D62615
D6227
DO2.D_E1
DO12 contact type
D6228
DO3.D_E1
DO13 contact type
D6229
DO4.D_E1
DO14 contact type
D6230
DO5.D_E1
DO15 contact type
D6231 to D6300
Summary of Contents for UTAdvanced Series
Page 17: ...Blank Page...
Page 77: ...Blank Page...
Page 285: ...Blank Page...
Page 325: ...Blank Page...
Page 467: ...Blank Page...
Page 557: ...Blank Page...
Page 825: ...Blank Page...
Page 861: ...Blank Page...
Page 863: ...Blank Page...
Page 865: ...Blank Page...