8-120
IM 05P07A01-01EN
8.4 UT35A/UT32A/UT32A-D/UP35A/UP32A D Registers
Check the Number of Segments, Copy and Clear of Program Pattern (D8971 to D8993)
Register
No.
Ref.
No.
H No.
Register
symbol
R/W
Description
Range and meaning of value
D8971 48971
230A PTN.S
R/W Pattern number designation for
comfirming number of segments
0: not select program pattern
1 to 2 (4 when the option “/AP” is specified.)
D8972 48972 230B USE.S
R
Number of segments within a
pattern
The number of the segment is displayed
when the program pattern number is specified
in the parameter PTN.S.
0: Not registered
1 to 20 (40 when the option “/AP” is
specified.)
D8974 to D8980
D8981
2315
2314 CPY.S
R/W Source-of-copying pattern number
designation
Set the source-of-copying pattern number
designation.
1 to 2 (4 when the option “/AP” is specified.)
D8982
2316
2315 CPY.D
R/W Target-of-copying pattern number
designation
Set the target-of-copying pattern number
designation.
1 to 2 (4 when the option “/AP” is specified.)
D8983
2317
2316 PTC.TRG
R/W Copy trigger
1: copy
D8984
2318
2317 PTN.ERR
R
Read/write error information
0: normal end
Except 0: error (See "Error information"
described later in this chapter.)
D8985 to D8990
D8991 48991 231E CLR.P
R/W Program pattern clearance
Set the number of program pattern erase.
1 to 2 (4 when the option “/AP” is specified.)
D8992 48992
231F CLR.TRG
R/W Clearance trigger
1:
clear
D8993 48993
2320 PTN.ERR
R
Read/write error information
0: normal end
Except 0: error (See "Error information"
described later in this chapter.)
D8994 to D9000
Modbus communication
The example for the communication command is Modbus/RTU. For easy understanding,
space is added but it is not present in the actual command. The device address is “1.”
How to check the number of segments used in one pattern
Example: Checking segment numbers used in pattern 1
(1) Write pattern number “1” to D8971 (PTN.S).
(2) Read from D8972 (USE.S).
(1) 01 10 230A 0001 02 0001 [CRC]
(2) 01 03 230B 0001 [CRC]
How to copy pattern
Example: Copying patterns1 to 2
(1) Write “1” to D8981 (CPY.S: Source-of-copying pattern number designation), “2” to
D8982 (CPY.D: Target-of-copying pattern number designation), and “1” to D8983
(PTC.TRG: Copy trigger).
If “PTN.ERR” in the response is other than zero, an error occurred. If zero, the write
was successful.
(1) 01 46 2314 0003 06 0001 0002 0001 [CRC]
How to clear pattern
Example: Clearing pattern 2
(1) Write “2” to D8911 (CLR.P: Program pattern clearance) and “1” to D8992 (CLR.TRG:
Clearance trigger).
If “PTN.ERR” in the response is other than zero, an error occurred. If zero, the write
was successful.
(1) 01 46 231E 0002 04 0002 0001 [CRC]