2-1
IM 05P07A01-01EN
Setting Communication Functions
2
2.1 Setting Parameters
2.1.1 Setting RS-485 Communication (for UTAdvanced with RS-485 communication)
This section describes the setting parameters and setting ranges of the UTAdvanced for
using the communication functions.
Set the required parameters referring to the UTAdvanced Operation Guide or User’s Manual.
Setting Display
Parameter Setting Display
UT75A/UT55A/UT35A:/UP55A/PU35A
Operation Display >
PARAMETER
and
Left arrow
keys
simultaneously for 3 seconds (to the [
CTL
] Menu Display) >
Right
arrow
key (to the [
R485
] Menu Display in E3 or E4
*1
) >
SET/ENTER
key (The setting parameter is displayed.)
*1: Only UT75A/UT55A/UP55A. UT35A/UP35A does not have R485 of E4.
(UT75A/UT55A/UP55A: E3 or E4 indicating the terminal area is displayed
on Group display. UT35A/UP35A: E3 indicating the terminal area is
displayed on Group display.)
UT52A/UT32A/UT32A-D/UP32A/UM33A:
Operation Display >
PARA
and
Left arrow
keys simultaneously for 3
seconds (to the [
CTL
] Menu Display) >
Right arrow
key (to the [
R485
]
Menu Display in E1) >
SET/ENTER
key (The setting parameter is
displayed.) (E1 indicating the terminal area is displayed on Group display.)
Setting Details
Parameter
symbol
Group
display
Name
Setting range
Menu symbol
Initial value
PSL
UT75A/
UT55A/
UP55A: E3
or E4
UT52A/
UT32A/
UT32A-D/
UT32A/
UM33A: E1
UT35A/
UP35A: E3
Protocol
selection
PC link communication
PCL (0)
R485
MBRTU (8)
PC link communication
(with checksum)
PCLSM (1)
Ladder communication
LADR (2)
Coordinated master station CO-M (3) *3
Coordinated slave station
CO-S (4) *4
Modbus (ASCII)
MBASC (7)
Modbus (RTU)
MBRTU (8)
Coordinated master
station (2-loop mode) CO-M2 (9) *5
Coordinated slave
station (Loop-1 mode) CO-S1 (10) *4
Coordinated slave
station (Loop-2 mode) CO-S2 (11) *4
Peer-to-peer
communication
P-P (12) *3
BPS
Baud rate
600 bps
600 (0)
19200 (5)
1200 bps
1200 (1)
2400 bps
2400 (2)
4800 bps
4800 (3)
9600 bps
9600 (4)
19200 bps
19200 (5)
38400 bps *1
38400 (6)
PRI
Parity
None
NONE (0)
EVEN (1)
Even
EVEN (1)
Odd
ODD (2)
STP
Stop bit
1 bit
1 (1)
1 (1)
2 bits
2 (2)
DLN
Data length
PC link
communication
7 bits (7)
8 bits (1)
8 bits (8)
Modbus (ASCII)
Fixed at 7 bits (0)
Ladder communication
Fixed at 8 bits (1)
ADR
Address
1 to 99
1
RP.T
*2
Minimum
response time
0 to 10 (x10ms)
0
Note: Figures in parentheses "( )" are values to be set when performing communication.
Chapter 2 Setting Communication Functions