14-88
IM 05P07A01-01EN
14.4 UT75A D Registers
Register
No.
Description
Range and meaning of value
D5541
HSR_E3
High-speed response mode
0: OFF, 1 to 8
D5542
BPS_E3
Baud rate
4: 9600 (9600 bps)
5: 19200 (19.2k bps)
6: 38400 (38.4k bps)
D5543
PRI_E3
Parity
0: NONE (None)
1: EVEN (Even)
2: ODD (Odd)
D5544
IP1_E3
IP address 1
0 to 255
Address : D5542.D5543.D5544.D5545
D5545
IP2_E3
IP address 2
D5546
I
P3_E3
IP address 3
D5547
IP4_E3
IP address 4
D5548
SM1_E3
Subnet mask 1
0 to 255
Address : D5546.D5547.D5548.D5549
D5549
SM2_E3
Subnet mask 2
D5550
SM3_E3
Subnet mask 3
D5551
SM4_E3
Subnet mask 4
D5552
DG1_E3
Default gateway 1
0 to 255
Address : D5550.D5551.D5552.D5553
D5553
DG2_E3
Default gateway 2
D5554
DG3_E3
Default gateway 3
D5555
DG4_E3
Default gateway 4
D5556
PRT_E3
Port number
502, 1024 to 65535
D5557
IPAR_E3
IP access restriction
0: OFF (Disable), 1: ON (Enable)
D5558
1.IP1_E3
Permitted IP address 1-1
0 to 255
Address : D5556.D5557.D5558.D5559
D5559
1.IP2_E3
Permitted IP address 1-2
D5560
1.IP3_E3
Permitted IP address 1-3
D5561
1.IP4_E3
Permitted IP address 1-4
D5562
2.IP1_E3
Permitted IP address 2-1
0 to 255
Address : D5560.D5561.D5562.D5563
D5563
2.IP2_E3
Permitted IP address 2-2
D5564
2.IP3_E3
Permitted IP address 2-3
D5565
2.IP4_E3
Permitted IP address 2-4
D5566
ESW_E3
Ethernet setting switch
0: OFF, 1: ON (Enable)
Setting this parameter to “1: ON” enables the Ethernet
communication parameter settings.
* The parameter ESW automatically returns to “0: OFF”
after “1: ON” is set.
D5567 to D5570
D5571
MAC1_E3
MAC address 1 *1
0000 to FFFF (Hex)
Arrangement: D5771, D5772, D5773
D5572
MAC2_E3
MAC address 2 *1
D5573
MAC3_E3
MAC address 3 *1
D5574 to D5580
D5581
BR_E3-C
*2
Baud rate
(for CC-link communication)
0: 156K (156k bps)
1: 625K (625k bps)
2: 2.5M (2.5M bps)
3: 5M (5M bps)
4: 10M (10M bps)
D5582
ADR_E3-C
*2
Address (for CC-link
communication)
1 to 64
D5583
BPS_E3-C
*2
Baud rate
(for CC-link communication)
4: 9600 (9600 bps)
5: 19200 (19.2k bps)
6: 38400 (38.4k bps)
D5584
FILE_E3-C
*2
Profile number (for CC-link
communication)
0, 21 to 25
D5585
SCAN_E3-C
*2
Automatic rescan time
(for CC-link communication)
0: OFF
1: 1M (1 minute)
2: 10M (10 minutes)
3: 30M (30 minutes)
4: 60M (60 minutes)
D5586 to D5590
*1: With regardds to the information on D5571 to D5573, three D registers comprise one
parameter data.
*2: Same parameter exists in other menu. “-C” is added to the end of the parameter in CC-L
menu (for CC-Link communication).