14-53
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT75A)
14
14.4 UT75A D Registers
Loop-2 Alarm Function Setting (D3901 to D4000)
Register
No.
Description
Range and meaning of value
D3901
AL1.T_L2
Alarm-1 type
A
L1.T_L1 to AL8.T_L1
00: Disable
01: PV high limit
02: PV low limit
03: SP high limit
04: SP low limit
05: Deviation high limit
06: Deviation low limit
07: Deviation high and low limits
08: Deviation within high and low limits
09: Target SP high limit
10: Target SP low limit
11: Target SP deviation high limit
12: Target SP deviation low limit
13: Target SP deviation high and low limits
14: Target SP deviation within high and low limits
15: OUT high limit
16: OUT low limit
17: Cooling-side OUT high limit
18: Cooling-side OUT low limit
19: Analog input PV high limit
20: Analog input PV low limit
21: Analog input PV2 high limit
22: Analog input PV2 low limit
23: Analog input AIN2 high limit
24: Analog input AIN2 low limit
25: Analog input AIN4 high limit
26: Analog input AIN4 low limit
27: Feedback input high limit
28: Feedback input low limit
29: PV velocity
30: Fault diagnosis
31: FAIL
32: Deviation(%) high limit
33: Deviation(%) low limit
34: Deviation(%) high and low limits
35: Deviation(%) within high and low limits
36: Target SP deviation(%) high limit
37: Target SP deviation(%) low limit
38: Target SP deviation(%) high and low limits
39: Target SP deviation(%) within high and low limits
A
L1.W_L1 to AL8.W_L1
0: Without Stand-by action
1: With Stand-by action
A
L1.D_L1 to AL8.D_L1
0: Alarm output: Energized
1: Alarm output: De-energized
A
L1.L_L1 to AL8.L_L1
0
: OFF
1: Latch 1
2: Latch 2
3: Latch 3
4: Latch 4
When the UTAdvanced parameter is set by key
stroke, the alarm type, stand-by action, energized/
de-energized, and latch comprise one parameter.
D3902
AL1.W_L2
Alarm-1 stand-by action
D3903
AL1.D_L2
A
larm-1 energized/de-energized
D3904
AL1.L_L2
Alarm-1 latch
D3905
AL2.T_L2
Alarm-2 type
D3906
AL2.W_L2
Alarm-2 stand-by action
D3907
AL2.D_L2
A
larm-2 energized/de-energized
D3908
AL2.L_L2
Alarm-2 latch
D3909
AL3.T_L2
Alarm-3 type
D3910
AL3.W_L2
Alarm-3 stand-by action
D3911
AL3.D_L2
A
larm-3 energized/de-energized
D3912
AL3.L_L2
Alarm-3 latch
D3913
AL4.T_L2
Alarm-4 type
D3914
AL4.W_L2
Alarm-4 stand-by action
D3915
AL4.D_L2
A
larm-4 energized/de-energized
D3916
AL4.L_L2
Alarm-4 latch
D3917
AL5.T_L2
Alarm-5 type
D3918
AL5.W_L2
Alarm-5 stand-by action
D3919
AL5.D_L2
A
larm-5 energized/de-energized
D3920
AL5.L_L2
Alarm-5 latch
D3921
AL6.T_L2
Alarm-6 type
D3922
AL6.W_L2
Alarm-6 stand-by action
D3923
AL6.D_L2
A
larm-6 energized/de-energized
D3924
AL6.L_L2
Alarm-6 latch
D3925
AL7.T_L2
Alarm-7 type
D3926
AL7.W_L2
Alarm-7 stand-by action
D3927
AL7.D_L2
A
larm-7 energized/de-energized
D3928
AL7.L_L2
Alarm-7 latch
D3929
AL8.T_L2
Alarm-8 type
D3930
AL8.W_L2
Alarm-8 stand-by action
D3931
AL8.D_L2
A
larm-8 energized/de-energized
D3932
AL8.L_L2
Alarm-8 latch
D3933
VT1_L2
P
V velocity alarm time setpoint 1
0.01 to 99.59 (m.s)
D3934
VT2_L2
P
V velocity alarm time setpoint 2
D3935
VT3_L2
P
V velocity alarm time setpoint 3
D3936
VT4_L2
P
V velocity alarm time setpoint 4
D3937
VT5_L2
P
V velocity alarm time setpoint 5
D3938
VT6_L2
P
V velocity alarm time setpoint 6
D3939
VT7_L2
P
V velocity alarm time setpoint 7
D3940
VT8_L2
P
V velocity alarm time setpoint 8