![YOKOGAWA UTAdvanced Series User Manual Download Page 708](http://html1.mh-extra.com/html/yokogawa/utadvanced-series/utadvanced-series_user-manual_3541677708.webp)
14-51
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT75A)
14
14.4 UT75A D Registers
Loop-2 SP and Alarm Setpoint Setting of Groups 1 to 8 (D3601 to D3800)
Register
No.
Description
Range and meaning of value
D3601
SP_L2_1
Target setpoint of group 1
0.0 to 100.0% of PV input range (EU) (Setting
range: SPL to SPH)
D3602
D3603
PIDN_L2_1
PID number selection of group 1
Set a PID group number to use.
1 to 16 (Depends on the PIDG. setting.)
D3604
A1_L2_1
Alarm-1 setpoint of group 1
S
et a display value of setpoint of PV alarm, SP
alarm, deviation alarm, output alarm, or velocity
alarm.
-19999 to 30000 (Set a value within the input
range.)
Decimal point position depends on the input type.
D3605
A2_L2_1
Alarm-2 setpoint of group 1
D3606
A3_L2_1
Alarm-3 setpoint of group 1
D3607
A4_L2_1
Alarm-4 setpoint of group 1
D3608
A5_L2_1
Alarm-5 setpoint of group 1
D3609
A6_L2_1
Alarm-6 setpoint of group 1
D3610
A7_L2_1
Alarm-7 setpoint of group 1
D3611
A8_L2_1
Alarm-8 setpoint of group 1
D3612
UPR_L2_1
SP ramp-up rate of group 1
Used to prevent SP from changing suddenly.
Set a ramp-up rate or ramp-down rate per hour or
minute. Set a time unit using the parameter TMU.
0: OFF (Disable)
0.0 + 1 digit to 100.0% of PV input range span (EUS)
D3613
DNR_L2_1
SP ramp-down rate of group 1
D3614 to D3620
D3621 to
D3631
SP_L2_2 to A8_L2_2
Target setpoint of group 2 to Alarm-8
setpoint of group 2
Same as D3601 to D3611
D3632
UPR_L2_2
SP ramp-up rate of group 2
Same as D3612 to D3613
D3633
DNR_L2_2
SP ramp-down rate of group 2
D3634 to D3640
D3641 to
D3651
SP_L2_3 to A8_L2_3
Target setpoint of group 3 to Alarm-8
setpoint of group 3
Same as D3601 to D3611
D3652
UPR_L2_3
SP ramp-up rate of group 3
Same as D3612 to D3613
D3653
DNR_L2_3
SP ramp-down rate of group 3
D3654 to D3660
D3661 to
D3671
SP_L2_4 to A8C_L2_4
Target setpoint of group 4 to Alarm-8
setpoint of group 4
Same as D3601 to D3611
D3672
UPR_L2_4
SP ramp-up rate of group 4
Same as D3612 to D3613
D3673
DNR_L2_4
SP ramp-down rate of group 4
D3674 to D3680
D3681 to
D3691
SP_L2_5 to A8_L2_5
Target setpoint of group 5 to Alarm-8
setpoint of group 5
Same as D3601 to D3611
D3692
UPR_L2_5
SP ramp-up rate of group 5
Same as D3612 to D3613
D3693
DNR_L2_5
SP ramp-down rate of group 5
D3694 to D3700
D3701 to
D3711
SP_L2_6 to A8_L2_6
Target setpoint of group 6 to Alarm-8
setpoint of group 6
Same as D3601 to D3611
D3712
UPR_L2_6
SP ramp-up rate of group 6
Same as D3612 to D3613
D3713
DNR_L2_6
SP ramp-down rate of group 6
D3714 to D3720
D3721 to
D3731
SP_L2_7 to A8_L2_7
Target setpoint of group 7 to Alarm-8
setpoint of group 7
Same as D3601 to D3611
D3732
UPR_L2_7
SP ramp-up rate of group 7
Same as D3612 to D3613
D3733
DNR_L2_7
SP ramp-down rate of group 7
D3734 to D3740
D3741 to
D3751
SP_L2_8 to A8_L2_8
Target setpoint of group 8 to Alarm-8
setpoint of group 8
Same as D3601 to D3611
D3752
UPR_L2_8
SP ramp-up rate of group 8
Same as D3612 to D3613
D3753
DNR_L2_8
SP ramp-down rate of group 8
D3754 to D3800
Summary of Contents for UTAdvanced Series
Page 17: ...Blank Page...
Page 77: ...Blank Page...
Page 285: ...Blank Page...
Page 325: ...Blank Page...
Page 467: ...Blank Page...
Page 557: ...Blank Page...
Page 825: ...Blank Page...
Page 861: ...Blank Page...
Page 863: ...Blank Page...
Page 865: ...Blank Page...