![background image](http://html1.mh-extra.com/html/omron/sysmac-cs1d-cpu/sysmac-cs1d-cpu_reference-manual_742268073.webp)
34
Instruction Functions
Section 2-2
2-2-4
Timer and Counter Instructions
Instruction
Mnemonic
Code
Symbol/Operand
Function
Location
Execution
condition
Page
HUNDRED-MS
TIMER
TIM
(BCD)
TIMX
(Binary)
(CS1-H, CJ1-H,
CJ1M, or CS1D
only)
Output
Required
246
TEN-MS TIMER
TIMH
015
(BCD)
TIMHX
551
(Binary)
(CS1-H, CJ1-H,
CJ1M, or CS1D
only)
TIMH(015)/TIMHX(551) operates a decrementing timer with units of
10-ms. The setting range for the set value (SV) is 0 to 99.99 s for BCD
and 0 to 655.35 s for binary (decimal or hexadecimal).
Output
Required
250
ONE-MS TIMER
TMHH
540
(BCD)
TMHHX
552
(BCD)
(CS1-H, CJ1-H,
CJ1M, or CS1D
only)
TMHH(540)/TMHHX(552) operates a decrementing timer with units of
1-ms. The setting range for the set value (SV) is 0 to 9.999 s for BCD
and 0 to 65.535 s for binary (decimal or hexadecimal).
Output
Required
254
TIM
N
S
N
:
Timer number
S
:
Set value
SV
SV
Timer input
Timer PV
Timer input
Timer PV
TIM/TIMX(550) operates a decrementing timer with units of 0.1-s.
The setting range for the set value (SV) is 0 to 999.9 s for BCD
and 0 to 6,553.5 s for binary (decimal or hexadecimal).
Completion
Flag
Completion
Flag
TIMX(550)
N
S
N
:
Timer number
S
:
Set value
TIMH(015)
N
S
N
:
Timer number
S
:
Set value
SV
SV
Timer input
Timer PV
Timer input
Timer PV
Completion
Flag
Completion
Flag
TIMHX(551)
N
S
N
:
Timer number
S
:
Set value
TMHH(540)
N
S
N
:
Timer number
S
:
Set value
SV
SV
Timer input
Timer PV
Timer input
Timer PV
Completion
Flag
Completion
Flag
TMHHX(552)
N
S
N
:
Timer number
S
:
Set value
Summary of Contents for SYSMAC CS1D-CPU**
Page 3: ...iv...
Page 29: ...xxx...
Page 185: ...146 List of Instructions by Function Code Section 2 4...
Page 1389: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2...
Page 1390: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits...
Page 1391: ...1352 ASCII Code Table Appendix A...