Conversion Instructions
Section 3-12
Description
BCDL(059) converts the 8-digit hexadecimal (32-bit binary) data in S and S+1
to 8-digit BCD data and writes the result to R and R+1.
Flags
Precautions
The content of S+1 and S must not exceed 05F5 E0FF (9999 9999 decimal).
Examples
The following diagram shows an example of 8-digit BCD-to-binary conversion.
When CIO 000000 is ON in the following example, the hexadecimal value in
CIO 0011 and CIO 0010 is converted to a BCD value and stored in D00200
and D00201.
EM Area without bank
E00000 to E32766
EM Area with bank
En_00000 to En_32766
(n = 0 to C)
Indirect DM/EM
addresses in binary
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
(n = 0 to C)
Indirect DM/EM
addresses in BCD
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
Constants
---
Data Registers
---
Index Registers
---
Indirect addressing
using Index Registers
,IR0 to ,IR15
–2048 to +2047 ,IR0 to –2048 to +2047 ,IR15
DR0 to DR15, IR0 to IR15
,IR0+(++) to ,IR15+(++)
,–(– –)IR0 to, –(– –)IR15
Area
S
R
R
R+1
(BCD)
(BCD)
S+1
S
(BIN)
(BIN)
Name
Label
Operation
Error Flag
ER
ON if the contents of S and S+1 exceed 05F5 E0FF
(9999 9999 decimal).
OFF in all other cases.
Equals Flag
=
ON if the result is 0.
OFF in all other cases.
R+1
R
×
16
3
×
16
2
×
16
1
×
16
0
×
16
7
×
16
6
×
16
5
×
16
4
×
10
3
×
10
2
×
10
1
×
10
0
×
10
7
×
10
6
×
10
5
×
10
4
Summary of Contents for SYSMAC CS1D-CPU**
Page 3: ...iv...
Page 29: ...xxx...
Page 185: ...146 List of Instructions by Function Code Section 2 4...
Page 1389: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2...
Page 1390: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits...
Page 1391: ...1352 ASCII Code Table Appendix A...