![background image](http://html1.mh-extra.com/html/omron/sysmac-cs1d-cpu/sysmac-cs1d-cpu_reference-manual_742268299.webp)
260
Timer and Counter Instructions
Section 3-6
Note
1.
If the IOM Hold Bit (A50012) has been turned ON, the status of timer Com-
pletion Flags and PVs will be maintained when the operating mode is
changed.
2.
If the IOM Hold Bit (A50012) has been turned ON and the status of the IOM
Hold Bit itself is protected in the PLC Setup, the status of timer Completion
Flags and PVs will be maintained even when the power is interrupted.
Note
When TIMU(541)/TIMUX(556) is in a program section between IL(002) and
ILC(003) and the program section is interlocked, the PV will be reset to the SV
and the Completion Flag will be turned OFF.
TIMU(541)/TIMUX(556) timers may not time accurately when used in a pro-
gram section jumped by the JMP(004), CJMP(510), CJPN(511), and
JME(005) instructions.
When a TIMU(541)/TIMUX(556) timer is forced set, its Completion Flag will
be turned ON. When a TIMU(541)/TIMUX(556) timer is forced reset, its Com-
pletion Flag will be turned OFF.
If online editing is used to overwrite a timer instruction, always reset the Com-
pletion Flag. The timer will not operate properly unless the Completion Flag is
reset.
A TIMU(541)/TIMUX(556) instruction’s Completion Flag is refreshed as
shown in the following table.
Operation Example
When timer input CIO 000000 goes from OFF to ON in this example, the timer
PV will begin counting down. The Timer Completion Flag, T0000, will be
turned ON after 12.3 ms.
When CIO 000000 goes OFF, the Timer Completion Flag, T0000, will be
turned OFF.
3-6-5
HUNDREDTH-MS TIMER: TMUH(544)/TMUHX(557)
Purpose
TMUH(544)/TMUHX(557) operates a decrementing timer with units of 0.01-
ms. The setting range for the set value (SV) is 0 to 0.09999 s for TMUH(544)
and 0 to 0.65535 s for TMUHX(557). The timer accuracy is –0.01 to 0 ms.
Note
These instructions can be used in the CJ1-H-R CPU Units only.
Execution of CNR(545)/CNRX(547), the RESET TIMER/
COUNTER instructions
OFF
Operation in interlocked program section
(IL(002)–ILC(003))
OFF
Operation in jumped program section
(JMP(004)–JME(005))
Retains previous status.
Condition
Completion Flag
Execution of TIMU(541)/
TIMUX(556)
The Completion Flag is turned ON if the SV is reached.
The Completion Flag is turned OFF if the SV has not been
reached.
or
TIMU
#0123
&0123
TIMUX
Summary of Contents for SYSMAC CS1D-CPU**
Page 3: ...iv...
Page 29: ...xxx...
Page 185: ...146 List of Instructions by Function Code Section 2 4...
Page 1389: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2...
Page 1390: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits...
Page 1391: ...1352 ASCII Code Table Appendix A...