769
Data Control Instructions
Section 3-18
Adjusting PID Parameters
The general relationship between PID parameters and control status is shown
below.
• When it is not a problem if a certain amount of time is required for stabili-
zation (settlement time), but it is important not to cause overshooting,
then enlarge the proportional band.
• When overshooting is not a problem but it is desirable to quickly stabilize
control, then narrow the proportional band. If the proportional band is nar-
rowed too much, however, then hunting may occur.
• When there is broad hunting, or when operation is tied up by overshooting
and undershooting, it is probably because integral action is too strong.
The hunting will be reduced if the integral time is increased or the propor-
tional band is enlarged.
• If the period is short and hunting occurs, it may be that the control system
response is quick and the derivative action is too strong. In that case, set
the derivative action lower.
SV
SV
Output
Output
Forward Action
Reverse Action
Low
temperature
High
temperature
Low
temperature
High
temperature
(MV output designation: 50%)
SV
Control by measured PID
When P is enlarged
SV
When P is narrowed
Control by measured PID
SV
Control by measured PID
(when loose hunting occurs)
Enlarge I or P.
SV
Control by measured PID
(when hunting occurs in a short period)
Lower D.
Summary of Contents for SYSMAC CS1D-CPU**
Page 3: ...iv...
Page 29: ...xxx...
Page 185: ...146 List of Instructions by Function Code Section 2 4...
Page 1389: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2...
Page 1390: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits...
Page 1391: ...1352 ASCII Code Table Appendix A...