156
Notation and Layout of Instruction Descriptions
Section 3-1
Constants
Constants input for operands are given as listed below.
Operand Descriptions and Operand Specifications
• Operands Specifying Bit Strings (Normally Input as Hexadecimal):
Only the hexadecimal form is given for operands specifying bit strings,
e.g., only “#0000 to #FFFF” is specified as the S operand for the
MOV(021) instruction. On the CX-Programmer, however, bit strings can
be input in decimal form by using the & prefix.
• Operands Specifying Numeric Values (Normally Input as Decimal, Includ-
ing Jump Numbers):
Both the decimal and hexadecimal forms are given for operands specify-
ing numeric values, e.g., “#0000 to #FFFF” and “&0 to &65535” are given
for the N operand for the XFER(070) instruction.
Operands
Operand Specifications
The memory areas addresses that can be used each operand are listed in a table
like the following one. The letters used in the column headings on the left are the
same as those used in the ladder symbol. “---” is used to indicate when an area can-
not be specific for an operand.
Area
S
C
D
CIO Area
CIO 0000 to CIO 6143
Work Area
W000 to W511
Holding Bit Area
H000 to H511
Auxiliary Bit Area
A000 to A959
A448 to A959
Timer Area
T0000 to T4095
Counter Area
C0000 to C4095
DM Area
D00000 to D32767
EM Area without
bank
E00000 to E32767
Description
The function of the instruction and the operands used in the instruction are
described.
Flags
The flags
table indicates the status of the condition flags immediately after execution
of the instruction. Any flags that are not listed are not affected by the instruction.
“OFF” indicates that a flag is turned OFF immediately after execution of the instruc-
tion regardless of the results of executing the instruction.
Name
Label
Operation
Error Flag
ER
ON if control data is within ranges.
OFF in all other cases.
Equals Flag
=
OFF
Negative Flag
N
OFF
Precautions
Special precautions required in using the instruction are provided. Be sure to read
and follow these precautions.
Example
An example of using the instruction with specific operands is provided to further
explain the function of the instruction.
Item
Contents
15
8
0
7
C
m
n
Where necessary, the meaning of words and bits used in specific operands, such
as control words, is given.
Source bit: 00 to 0F
(0 to 15 decimal)
Destination bit: 00 to 0F
(0 to 15 decimal)
Summary of Contents for SYSMAC CS1D-CPU**
Page 3: ...iv...
Page 29: ...xxx...
Page 185: ...146 List of Instructions by Function Code Section 2 4...
Page 1389: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2...
Page 1390: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits...
Page 1391: ...1352 ASCII Code Table Appendix A...