36
Instruction Functions
Section 2-2
ACCUMULATIVE
TIMER
TTIM
087
(BCD)
TTIMX
555
(Binary)
(CS1-H, CJ1-H,
CJ1M, or CS1D
only)
Output
Required
263
LONG TIMER
TIML
542
(BCD)
TIMLX
553
(Binary)
(CS1-H, CJ1-H,
CJ1M, or CS1D
only)
Output
Required
267
Instruction
Mnemonic
Code
Symbol/Operand
Function
Location
Execution
condition
Page
TTIM(087)
N
S
Timer
input
Reset
input
N
:
Timer number
S
:
Set value
SV
Timer input
Timer PV
Completion
Flag
Reset input
PV maintained.
Timing resumes.
TTIM(087)/TTIMX(555) operates an incrementing timer with units of
0.1-s. The setting range for the set value (SV) is 0 to 999.9 s for
BCD and 0 to 6,553.5 s for binary (decimal or hexadecimal).
TTIMX(555)
N
S
N
:
Timer number
S
:
Set value
Reset
input
Timer
input
TIML(542)
D1
D2
S
D1
:
Completion
Flag
D2
:
PV word
S
:
SV word
SV
Timer input
Timer PV
Completion Flag
(Bit 00 of D1)
TIML(542)/TIMLX(553) operates a decrementing timer with units of
0.1-s that can time up to approx. 115 days for BCD and 49,710 days
for binary (decimal or hexadecimal).
TIMLX(553)
D1
D2
S
D1
:
Completion
Flag
D2
:
PV word
S
:
SV word
Summary of Contents for SYSMAC CS1D-CPU**
Page 3: ...iv...
Page 29: ...xxx...
Page 185: ...146 List of Instructions by Function Code Section 2 4...
Page 1389: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2...
Page 1390: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits...
Page 1391: ...1352 ASCII Code Table Appendix A...