background image

 
 

PRT-

PX1

6

-PCB

 

Protege 16 PGM Output Expander 

Installation Manual 
 

Summary of Contents for Protege PRT-PX16-PCB

Page 1: ...PRT PX16 PCB Protege 16 PGM Output Expander Installation Manual...

Page 2: ...produced photocopied or transmitted in any form or by any means electronic or mechanical for any purpose without the express written permission of Integrated Control Technology Limited Designed and ma...

Page 3: ...______________________ 14 3 1 Trouble Zone Inputs 14 4 Programmable Outputs ___________________________________________________ 15 4 1 PGM Outputs 1 to 16 15 5 Elevator Floor Relay Connections________...

Page 4: ...__________________________ 26 10 New Zealand and Australia ________________________________________________ 27 11 European Standards ______________________________________________________ 28 12 Orderi...

Page 5: ...nnected to the RS 485 Module Network Up to 250 modules can be connected to the Protege System in any combination to the network up to a distance of 900M 3000ft Communication beyond this distance requi...

Page 6: ...low to the vents of the enclosure are not restricted We recommend the PGM Expander is installed in a location that will facilitate easy access for wiring We also recommend that the PGM Expander is ins...

Page 7: ...TP TP Tamper Input Connection 2 4 Earth Ground Connection The Analog Output Expander has a connection for earth ground For best results a cold water pipe should be used with a pipe wiring clamp If a...

Page 8: ...he electrical termination point inside the enclosure and the secondary wires of the transformer to the AC Input on the controller i Termination of wiring to the PGM Expander while power is applied or...

Page 9: ...conds this allows the status and condition of the battery to be detected On completion of this first test the normal testing period of 10 minutes will be resumed 2 7 Status Indicator The status output...

Page 10: ...e than one 12V supply may cause failure or damage to the PGM Expander or device supplying network power i The EOL End Of Line jumper setting MUST be set in the ON position for the LAST module on the R...

Page 11: ...the following diagram NA N N NB S S SB AUX SA AUX NA N N NB Next Floor Control Module Reader Expander Supplying Network Power Slave Devices Connected to the Reader Expander Slave Communication Interfa...

Page 12: ...otege Intelligent Reader Expander 2 11 Fire Control Input The fire control input is an optically isolated input that allows the output relays of the Protege PGM Expander to be deactivated in the case...

Page 13: ...tion is provided on the Protege PGM Expander to disable the Fire Control Input when it is not being used Using this configuration jumper a wire loop is not required from the and terminals to the F and...

Page 14: ...nitor the status of the PGM expander and in most cases are not physically connected to an external zone input For example trouble zone PX001 04 is used to monitor the auxiliary voltage output and will...

Page 15: ...each have a FORM C output relay and an indicator showing the relay status The connection example below shows the control of an external LED indicator from the auxiliary supply of the 16 PGM Output Exp...

Page 16: ...Elevator Controller will operate in a fail safe mode Fire Complete Power Failure or Communications Loss if enabled will still allow access to the floors that are being controlled Floor Selection Butto...

Page 17: ...g the NO and COM relay contacts as shown in the following diagram This will only allow access to a floor if the relay is activated Deactivation of the relay or complete power failure will PREVENT any...

Page 18: ...l Board NC NO COM RELAY 1 Normal Connection Removed Floor Input Terminals in Elevator Control System Floor Selection Button in Elevator Car IN1 IN2 Destination Reporting Fail Safe Wiring As shown in t...

Page 19: ...terminal on the PRT PX16 DRI Destination Reporting Interface A button voltage common wire is also required from the elevator control system The button common voltage wire is typically looped to all t...

Page 20: ...ill allow you to understand the principles and operation of the unit prior to the installation taking place AC AC B B ST Power connector on main elevator control board IN1 IN2 Inputs on the DRM daught...

Page 21: ...8 5 ADDRESS 16 6 ADDRESS 32 7 ADDRESS 64 8 ADDRESS 128 Normal CONFIG Switch Functions 1 ADDRESS 1 2 ADDRESS 2 3 ADDRESS 4 4 ADDRESS 8 5 ELEVATOR MODE 6 7 8 ELEVATOR MODE ELEVATOR MODE ELEVATOR MODE E...

Page 22: ...nder and the floors that it will control Reader 1 floor 1 starts at address 1 and reader 2 floor 1 starts at address 9 Elevator Car 1 Floor Address Configuration Elevator Car 2 Floor Address Configura...

Page 23: ...erating in firmware update mode or there is no firmware loaded The fault indicator when ON indicates that an error has occurred while trying to register with the system controller The status indicator...

Page 24: ...ed interface 7 7 Relay Ok Power to the relays onboard is controlled by the F and F terminals and can be overridden by the FIRE OVERRIDE jumper When power is supplied to the relays the RELAY OK indicat...

Page 25: ...pander is not compatible with the system controller To clear this error update the module using the module update application 3 Address Too High The Output Expander address is above the maximum number...

Page 26: ...0mA Max Open Collector Inputs Tamper Normally Closed Fire Control 12 32VDC 6 21mA Voltage Input Button Inputs Optional 16 Requires PRT PX16 DRI Interface Dimensions PCB Dimensions 183mm X 234mm 7 2 X...

Page 27: ...Output Expander Installation Manual June 2017 27 10 New Zealand and Australia General Product Statement The RCM compliance label indicates that the supplier of the device asserts that it complies wit...

Page 28: ...designated collection point Penalties may be applicable for incorrect disposal of this waste in accordance with you national legislation For business users in the European Union If you wish to discar...

Page 29: ...e selected To comply with EN 50131 1 Single Button Setting should not be selected To comply with EN 50131 1 only one battery can be connected and monitored per system If more capacity is required a si...

Page 30: ...2 Ordering Information Please use the following product codes when placing an order for the Protege PGM Expander PRT PX16 PCB Protege 16 PGM Output Expander PCB Only Includes Accessory Bag Manuals and...

Page 31: ...any component of the elevator system This includes the wiring of the Elevator Controller s floor control relay terminals Under no circumstances does Integrated Control Technology or any associated co...

Page 32: ...the products and because the products may be used in conjunction with products not manufactured by ICT ICT cannot guarantee the performance of the security system ICT s obligation and liability under...

Page 33: ...below Integrated Control Technology P O Box 302 340 North Harbour Post Centre Auckland New Zealand 4 John Glenn Ave Rosedale North Shore City 0632 Auckland New Zealand Phone 64 9 476 7124 Toll Free N...

Page 34: ...590494 Designers manufacturers of integrated electronic access control security and automation products Designed manufactured by Integrated Control Technology Ltd Copyright Integrated Control Technol...

Reviews: