Chapter 5 Internal Memory and I/O Signal
5-13
XPM_ECON), when a network cable is not connected, servo connection command will not be executed
and when a network cable is connected, servo connection command will be executed. Then you can
prevent the unnecessary error.
(3) JOG Operation
(a) Forward/Reverse Jog Signals show the direction of Jog Operation. The Jog operation shall be divided into
Forward/Reverse direction according to the On/Off signals. When Forward Jog Signal is On, it starts
Forward Operation and When Jog Signal is Off, it starts Reverse Operation. When both signals Off, it
stops Jog Signals. When both signals On, it does Forward Jog Signal.
Forward Jog Signal
Reverse Jog Signal
Jog Operation Status
On
Off
Forward Jog Operation
Off
On
Reverse Jog Operation
Off
Off
Stop
On
On
Forward Jog Operation
(b) If Jog direction is changed during Jog operation, it slows down at first and then operates as the direction it
changed.
(c) According to value of Jog low/high Signals, it could operate with low/high speed. When jog low/high signals
Off, it operates with low speed and when they are ON, it operates with high speed.
(d) If you change value of low/high jog signals during Jog operation, there will be no stop and apply the speed
as you changed.
Time
Speed
JOG in
Operation
JOG Low/High
Speed Signal
Forward JOG
Signal
Reverse JOG
Signal
JOG High Speed
JOG Low Speed
JOG Low Speed
JOG High Speed