Table 456:
COUVGAPC (59_27) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
R1
0.01 - 3000.00
ohm
0.01
5.00
Positive sequence resistance per phase for
the line in ohm
X1
0.01 - 3000.00
ohm
0.01
40.00
Positive sequence reactance per phase for
the line in ohm
Xc
1.00 - 10000.00
ohm
0.01
1000.00
Half of equivalent capacitive reactance per
phase in ohm
EnShuntReactor
Disabled
Enabled
-
-
Enabled
Enable setting if shunt reactor connected in line
Xsh
1.00 - 10000.00
ohm
0.01
1500.00
Per phase reactance of local Shunt Reactor
in ohm
13.8.3.6
Technical data
Table 457:
COUVGAPC (59_27)technical data
Function
Range or value
Accuracy
Operate value,
undervoltage
(1-100)% of VBase
± 0,5% of V
n
Reset ratio, undervoltage
<105%
-
Critical impulse time,
undervoltage
5 ms typically at 1.2 to 0.8xV
set
-
Impulse margin time,
undervoltage
15 ms typically
-
Operate value,
overvoltage
(1-200)% of VBase
± 0.5% of V
n
at V<V
n
± 0.5% of V at V>V
n
Reset ratio, overvoltage
>95%
-
Critical impulse time,
overvoltage
2 ms typically at 0.8 to 1.2xV
set
-
Impulse margin time,
overvoltage
10 ms typically
-
Timers
(0.000-60.000) s
± 0.5% ± 10 ms
13.8.4
Sudden change in current variation SCCVPTOC (51)
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Sudden change in current variation
SCCVPTOC
-
51
1MRK505222-UUS C
Section 13
Scheme communication
839
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...