Table 2:
TRM_12I Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CT_WyePoint1
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec1
1 - 10
A
1
1
Rated CT secondary current
CTprim1
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint2
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec2
1 - 10
A
1
1
Rated CT secondary current
CTprim2
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint3
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec3
1 - 10
A
1
1
Rated CT secondary current
CTprim3
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint4
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec4
1 - 10
A
1
1
Rated CT secondary current
CTprim4
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint5
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec5
1 - 10
A
1
1
Rated CT secondary current
CTprim5
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint6
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec6
1 - 10
A
1
1
Rated CT secondary current
CTprim6
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint7
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec7
1 - 10
A
1
1
Rated CT secondary current
CTprim7
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint8
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec8
1 - 10
A
1
1
Rated CT secondary current
CTprim8
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint9
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec9
1 - 10
A
1
1
Rated CT secondary current
CTprim9
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint10
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec10
1 - 10
A
1
1
Rated CT secondary current
Table continues on next page
Section 2
1MRK505222-UUS C
Analog inputs
48
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...