Test
Type test values
Reference standards
Radiated electromagnetic field
disturbance
20 V/m, 80-1000 MHz
1.4-2.7 GHz
IEC 60255-22-3
Radiated electromagnetic field
disturbance
35 V/m
26-1000 MHz
IEEE/ANSI C37.90.2
Conducted electromagnetic field
disturbance
10 V, 0.15-80 MHz
IEC 60255-22-6
Radiated emission
30-1000 MHz
IEC 60255-25
Conducted emission
0.15-30 MHz
IEC 60255-25
Table 724:
Insulation
Test
Type test values
Reference standard
Dielectric test
2.0 kV AC, 1 min.
ANSI C37.90
Impulse voltage test
5 kV, 1.2/50
m
s, 0.5 J
Insulation resistance
>100 M
W
at 500 VDC
Table 725:
Environmental tests
Test
Type test value
Reference standard
Cold test
Test Ad for 16 h at -25°C
IEC 60068-2-1
Storage test
Test Ad for 16 h at -40°C
IEC 60068-2-1
Dry heat test
Test Bd for 16 h at +70°C
IEC 60068-2-2
Damp heat test, steady state
Test Ca for 4 days at +40 °C and
humidity 93%
IEC 60068-2-78
Damp heat test, cyclic
Test Db for 6 cycles at +25 to +55
°C and humidity 93 to 95% (1
cycle = 24 hours)
IEC 60068-2-30
Table 726:
CE compliance
Test
According to
Immunity
EN 50263
Emissivity
EN 50263
Low voltage directive
EN 50178
Section 19
1MRK505222-UUS C
IED hardware
1156
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...