8.6.4
Input and output signals
Table 280:
LOVPTUV (27) Input signals
Name
Type
Default
Description
V3P
GROUP
SIGNAL
-
Voltage connection
BLOCK
BOOLEAN
0
Block the all outputs
CBOPEN
BOOLEAN
0
Circuit breaker open
VTSU
BOOLEAN
0
Block from voltage circuit supervision
Table 281:
LOVPTUV (27) Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip signal
PICKUP
BOOLEAN
Pickup signal
8.6.5
Setting parameters
Table 282:
LOVPTUV (27) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Enable/Disable
VBase
0.1 - 9999.9
kV
0.1
400.0
Base voltage
VPG
1 - 100
%VB
1
70
Pickup voltage in % of base voltage Vbase
tTrip
0.000 - 60.000
s
0.001
7.000
Operate time delay
Table 283:
LOVPTUV (27) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
tPulse
0.050 - 60.000
s
0.001
0.150
Duration of TRIP pulse
tBlock
0.000 - 60.000
s
0.001
5.000
Time delay to block when all 3ph voltages are
not low
tRestore
0.000 - 60.000
s
0.001
3.000
Time delay for enable the function after
restoration
Section 8
1MRK505222-UUS C
Voltage protection
548
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...