Name
Values (Range)
Unit
Step
Default
Description
BlkLowCurr_UC1
0 - 150
%IB
1
20
Internal low current blocking level for UC1 in
% of Ibase
PickupCurr_UC1
2.0 - 150.0
%IB
1.0
70.0
Operate undercurrent level for UC1 in % of
Ibase
tDef_UC1
0.00 - 6000.00
s
0.01
0.50
Independent (definitive) time delay of UC1
tResetDef_UC1
0.00 - 6000.00
s
0.01
0.00
Reset time delay used in IEC Definite Time
curve UC1
HarmRestr_UC1
Disabled
Enabled
-
-
Disabled
Enable block of UC1 by 2nd harmonic restrain
Operation_UC2
Disabled
Enabled
-
-
Disabled
Disable/Enable operation of UC2
EnBlkLowI_UC2
Disabled
Enabled
-
-
Disabled
Enable internal low current level blocking for
UC2
BlkLowCurr_UC2
0 - 150
%IB
1
20
Internal low current blocking level for UC2 in
% of Ibase
PickupCurr_UC2
2.0 - 150.0
%IB
1.0
70.0
Operate undercurrent level for UC2 in % of
Ibase
tDef_UC2
0.00 - 6000.00
s
0.01
0.50
Independent (definitive) time delay of UC2
HarmRestr_UC2
Disabled
Enabled
-
-
Disabled
Enable block of UC2 by 2nd harmonic restrain
Operation_OV1
Disabled
Enabled
-
-
Disabled
Disable/Enable operation of OV1
PickupVolt_OV1
2.0 - 200.0
%VB
0.1
150.0
Operate voltage level for OV1 in % of Vbase
CurveType_OV1
Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve
-
-
Definite time
Selection of time delay curve type for OV1
tDef_OV1
0.00 - 6000.00
s
0.01
1.00
Operate time delay in sec for definite time use
of OV1
tMin_OV1
0.00 - 6000.00
s
0.01
0.05
Minimum operate time for Inverse-Time
curves for OV1
TD_OV1
0.05 - 999.00
-
0.01
0.30
Time multiplier for the dependent time delay
for OV1
Operation_OV2
Disabled
Enabled
-
-
Disabled
Disable/Enable operation of OV2
PickupVolt_OV2
2.0 - 200.0
%VB
0.1
150.0
Pickup voltage for OV2 in % of Vbase
CurveType_OV2
Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve
-
-
Definite time
Selection of time delay curve type for OV2
tDef_OV2
0.00 - 6000.00
s
0.01
1.00
Operate time delay in sec for definite time use
of OV2
tMin_OV2
0.00 - 6000.00
s
0.01
0.05
Minimum operate time for Inverse-Time
curves for OV2
Table continues on next page
1MRK505222-UUS C
Section 10
Multipurpose protection
589
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...