ANSI05000170 V1 EN
Figure 294:
CVGAPC function main logic diagram for built-in protection elements
can be summarized as follows:
1. The selected currents and voltage are given to built-in protection elements. Each
protection element and step makes independent decision about status of its
PICKUP and TRIP output signals.
2. More detailed internal logic for every protection element is given in the following
four figures
3. Common PICKUP and TRIP signals from all built-in protection elements & steps
(internal OR logic) are available from multipurpose function as well.
Second
harmonic check
Selected voltage
X
PickupCurr_OC1
a
b
a>b
Voltage
control or
restraint
feature
OC1=On
BLKOC1
Directionality
check
Current
Restraint
Feature
I
measured
> k I
restraint
DIR_OK
Inverse
0-DEF
DEF time
selected
Inverse
time
selected
OR
Enable
second
harmonic
en05000831_ansi.vsd
Selected current
PU_OC1
TROC1
AND
BLKTROC1
Selected restrain current
AND
NOT
0
ANSI05000831 V1 EN
Figure 295:
Simplified internal logic diagram for built-in first overcurrent step that is, OC1 (step OC2 has the
same internal logic)
1MRK505222-UUS C
Section 10
Multipurpose protection
581
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...