Table 307:
CCSRDIF (87) Output signals
Name
Type
Description
FAIL
BOOLEAN
Detection of current circuit failure
ALARM
BOOLEAN
Alarm for current circuit failure
11.1.5
Setting parameters
Table 308:
CCSRDIF (87) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Disable/Enable Operation
IBase
1 - 99999
A
1
3000
IBase value for current pickup detectors
IMinOp
5 - 200
%IB
1
20
Minimum operate current differential pickup in
% of IBase
Table 309:
CCSRDIF (87) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
Pickup_Block
5 - 500
%IB
1
150
Block of the function at high phase current, in
% of IBase
11.1.6
Technical data
Table 310:
CCSRDIF (87) technical data
Function
Range or value
Accuracy
Operate current
(5-200)% of I
n
±
10.0% of I
n
at I
£
I
n
±
10.0% of I at I > I
n
Block current
(5-500)% of I
n
±
5.0% of I
n
at I
£
I
n
±
5.0% of I at I > I
n
11.2
Fuse failure supervision SDDRFUF
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Fuse failure supervision
SDDRFUF
-
-
Section 11
1MRK505222-UUS C
Secondary system supervision
600
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...