Table 45:
SMAI1 Output signals
Name
Type
Description
SPFCOUT
REAL
Number of samples per fundamental cycle from
internal DFT reference function
AI3P
GROUP SIGNAL
Group 1 analog input 3-phase group
AI1
GROUP SIGNAL
Group 1 analog input 1
AI2
GROUP SIGNAL
Group 1 analog input 2
AI3
GROUP SIGNAL
Group 1 analog input 3
AI4
GROUP SIGNAL
Group 1 analog input 4
AIN
GROUP SIGNAL
Group 1 analog input residual for disturbance recorder
Table 46:
SMAI2 Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block group 2
GRP2_A
STRING
-
Sample input to be used for group 2 phase A
calculations
GRP2_B
STRING
-
Sample input to be used for group 2 phase B
calculations
GRP2_C
STRING
-
Sample input to be used for group 2 phase C
calculations
GRP2_N
STRING
-
Sample input to be used for group 2 residual
calculations
Table 47:
SMAI2 Output signals
Name
Type
Description
AI3P
GROUP SIGNAL
Group 2 analog input 3-phase group
AI1
GROUP SIGNAL
Group 2 analog input 1
AI2
GROUP SIGNAL
Group 2 analog input 2
AI3
GROUP SIGNAL
Group 2 analog input 3
AI4
GROUP SIGNAL
Group 2 analog input 4
AIN
GROUP SIGNAL
Group 2 analog input residual for disturbance recorder
4.12.6
Setting parameters
Settings
DFTRefExtOut
and
DFTReference
shall be set to default value
InternalDFTRef
if no VT inputs are available. Internal nominal
frequency DFT reference is then the reference.
Section 4
1MRK505222-UUS C
Basic IED functions
112
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...