13.7.1
Introduction
Current reversal and weak-end infeed logic for phase segregated communication
(ZC1WPSCH, 85) function is used to prevent unwanted operations due to current
reversal when using permissive overreach protection schemes in application with
parallel lines when the overreach from the two ends overlaps on the parallel line.
The weak-end infeed logic is used in cases where the apparent power behind the
protection can be too low to activate the distance protection function. When activated,
received carrier signal together with local under voltage criteria and no reverse zone
operation gives an instantaneous trip. The received signal is also echoed back to
accelerate the sending end.
13.7.2
Principle of operation
13.7.2.1
Current reversal logic
The current reversal logic uses a reverse zone connected to the input IRVLx to
recognize the fault on the parallel line in phase Lx. When the reverse zone has been
activated for a certain settable time
tPickUpRev
it prevents sending of a
communication signal and activation of trip signal for a predefined time
tDelayRev
.
This makes it possible for the carrier receive signal to reset before the carrier aided trip
signal is activated due to the current reversal by the forward directed zone, see figure
.
IRVLn
IRVBLKLn
IRVOPLn
t
tDelayRev
&
t
tPickUpRev
t
10 ms
t
tPickUpRev
IEC06000474_2_en.vsd
IEC06000474 V2 EN
Figure 409:
Current reversal logic
The preventing of sending carrier send signal CSLn and activating of the TRIPLn in
the Scheme communication logic for distance or Overcurrent protection (ZCPSCH ,85)
is carried out by connecting the IRVOPLn signal to input BLOCKLn in ZCPSCH (85)
function.
The Current reversal and weak-end infeed logic for phase segregated communication
(ZC1WPSCH ,85) function has an internal 10 ms drop-off timer which secure that the
current reversal logic will be activated for short input signals even if the pick-up timer
is set to zero.
1MRK505222-UUS C
Section 13
Scheme communication
823
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...