Table 173:
PSPPPAM (78) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
IBase
0.1 - 99999.9
A
0.1
3000.0
Base Current (primary phase current in
Amperes)
Vbase
0.1 - 9999.9
kV
0.1
20.0
Base Voltage (primary phase-to-phase
voltage in kV)
MeasureMode
PosSeq
AB
BC
CA
-
-
PosSeq
Measuring mode (PosSeq, AB, BC, CA)
InvertCTcurr
No
Yes
-
-
No
Invert current direction
6.13.6
Technical data
Table 174:
PSPPPAM (78) technical data
Function
Range or value
Accuracy
Impedance reach
(0.00–1000.00)% of Zbase
± 2.0% of Vn/In
Characteristic angle
(72.00–90.00) degrees
± 5.0 degrees
Start and trip angles
(0.0–180.0) degrees
± 5.0 degrees
Zone 1 and Zone 2 trip counters
(1-20)
-
6.14
Automatic switch onto fault logic, voltage and current
based ZCVPSOF
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Automatic switch onto fault logic,
voltage and current based
ZCVPSOF
-
-
6.14.1
Introduction
Automatic switch onto fault logic, voltage and current based (ZCVPSOF) is a function
that gives an instantaneous trip at closing of breaker onto a fault. A dead line detection
check is provided to activate the function when the line is dead.
Mho distance protections can not operate for switch onto fault condition when the
phase voltages are close to zero. An additional logic based on VI Level is used for this
purpose.
Section 6
1MRK505222-UUS C
Impedance protection
368
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...