Function
Range or value
Accuracy
Time delay for energizing check
(0.000-60.000) s
± 0.5% ± 10 ms
Operate time for synchronism
check function
160 ms typically
-
Operate time for energizing
function
80 ms typically
-
12.2
Autorecloser SMBRREC (79)
Function Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Autorecloser
SMBRREC
O->I
SYMBOL-L V1 EN
79
12.2.1
Introduction
The autorecloser SMBRREC, 79 function provides high-speed and/or delayed auto-
reclosing for single or multi-breaker applications.
Up to five three-phase reclosing attempts can be included by parameter setting. The
first attempt can be single-, two and/or three pole for single pole or multi-pole faults
respectively.
Multiple autoreclosing functions are provided for multi-breaker arrangements. A
priority circuit allows one circuit breaker to close first and the second will only close if
the fault proved to be transient.
Each autoreclosing function is configured to co-operate with the synchronism check
function.
12.2.2
Principle of operation
12.2.2.1
Logic Diagrams
The logic diagrams below illustrate the principles applicable in the understanding of
the functionality.
1MRK505222-UUS C
Section 12
Control
633
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...