9.3.3
Function block
ANSI06000281-2-en.vsd
SAPFRC (81)
V3P*
BLOCK
BLKTRIP
BLKREST
TRIP
PICKUP
RESTORE
BLKDMAGN
ANSI06000281 V2 EN
Figure 287:
SAPFRC (81) function block
9.3.4
Input and output signals
Table 293:
SAPFRC (81) Input signals
Name
Type
Default
Description
V3P
GROUP
SIGNAL
-
Group signal for voltage input
BLOCK
BOOLEAN
0
Block of function
BLKTRIP
BOOLEAN
0
Blocking operate output.
BLKREST
BOOLEAN
0
Blocking restore output.
Table 294:
SAPFRC (81) Output signals
Name
Type
Description
TRIP
BOOLEAN
Operate/trip signal for frequencyGradient
PICKUP
BOOLEAN
Start/pick-up signal for frequencyGradient
RESTORE
BOOLEAN
Restore signal for load restoring purposes.
BLKDMAGN
BOOLEAN
Blocking indication due to low magnitude.
9.3.5
Setting parameters
Table 295:
SAPFRC (81) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Disable/Enable Operation
VBase
0.05 - 2000.00
kV
0.05
400.00
Base setting for the phase-phase voltage in kV
PUFreqGrad
-10.00 - 10.00
Hz/s
0.01
0.50
Frequency gradient start value. Sign defines
direction.
IntBlockLevel
0 - 100
%VB
1
50
Internal blocking level in % of VBase.
tTrip
0.000 - 60.000
s
0.001
0.200
Operate time delay in pos./neg. frequency
gradient mode.
Table continues on next page
1MRK505222-UUS C
Section 9
Frequency protection
565
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...