5.3.6
Technical data
Table 92:
STSGGIO (11) technical data
Function
Range or value
Accuracy
Operate current, zero sequence
(1-100)% of lBase
±1,0% of I
n
Operate current, low operation
(1-100)% of lBase
±1,0% of I
n
Operate voltage, phase to neutral
(1-100)% of VBase
± 0,5% of V
n
Operate voltage, phase to phase
(1-100)% of VBase
± 0,5% of V
n
Timers, general
(0.000-60.000) s
± 0.5% ± 10 ms
Critical impulse time
10 ms typically at 0.5 to.2 x Iset
-
Impulse margin time
20 ms typically
-
Transient overreach
< 2% at τ = 100 ms
-