R
X
Distance measuring zone
Phase selection
”Quadrilateral” zone
IEC09000049-1-en.vsd
)
/
(
phase
W
)
/
(
phase
W
IEC09000049 V1 EN
Figure 108:
Operating characteristic for FDPSPDIS (21) in forward direction for
three-phase fault, ohm/phase domain
The result from rotation of the load characteristic at a fault between two phases is
presented in fig
. Since the load characteristic is based on the same measurement as
the quadrilateral characteristic, it will rotate with the quadrilateral characteristic
clockwise by 30 degrees when subject to a pure phase-to-phase fault. At the same time
the characteristic will "shrink" by 2/√3, from the full
RLdFw
and
RLdRv
reach, which
is valid at load or three-phase fault.
1MRK505222-UUS C
Section 6
Impedance protection
229
Technical reference manual