Table 568:
CMSQI technical data
Function
Range or value
Accuracy
Current positive sequence, I1
Three phase settings
(0.1–4.0) × I
n
±
0.2% of I
n
at I ≤ 0.5 × I
n
±
0.2% of I at I > 0.5 × I
n
Current zero sequence, 3I0
Three phase settings
(0.1–1.0) × I
n
±
0.2% of I
n
at I ≤ 0.5 × I
n
±
0.2% of I at I > 0.5 × I
n
Current negative sequence, I2
Three phase settings
(0.1–1.0) × I
n
±
0.2% of I
n
at I ≤ 0.5 × I
n
±
0.2% of I at I > 0.5 × I
n
Phase angle
(0.1–4.0) × I
n
±
0.5° at 0.2 × I
n
< I < 0.5 × I
n
±
0.2° at 0.5 × I
n
≤ I < 4.0 × I
n
Table 569:
VMSQI technical data
Function
Range or value
Accuracy
Voltage positive sequence, U1
(10 to 300) V
±
0.3% of V at V ≤ 50 V
±
0.2% of V at V > 50 V
Voltage zero sequence, 3U0
(10 to 300) V
±
0.3% of V at V ≤ 50 V
±
0.2% of V at V > 50 V
Voltage negative sequence, U2
(10 to 300) V
±
0.3% of V at V ≤ 50 V
±
0.2% of V at V > 50 V
Phase angle
(10 to 300) V
±
0.3° at V ≤ 50 V
±
0.2° at V > 50 V
15.2
Event counter CNTGGIO
15.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Event counter
CNTGGIO
S00946 V1 EN
-
15.2.2
Introduction
Event counter (CNTGGIO) has six counters which are used for storing the number of
times each counter input has been activated.
Section 15
1MRK505222-UUS C
Monitoring
928
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...