R
X
RLdFwd
RLdRev
LdAngle
LdAngle
LdAngle
LdAngle
en05000196_ansi.vsd
ANSI05000196 V1 EN
Figure 173:
Characteristic of load encroachment function
The influence of load encroachment function on the operation characteristic is
dependent on the chosen operation mode of FRPSPDIS (21) function. When output
signal PHSELZ is selected, the characteristic for FRPSPDIS (21) (and also zone
measurement depending on settings) will be reduced by the load encroachment
characteristic, see figure
When output signal PHSELI is selected, the operation characteristic will be as in
figure
. The reach will in this case be limit by the minimum operation current and
the distance measuring zones.
Section 6
1MRK505222-UUS C
Impedance protection
334
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...