7.2.6
Technical data
Table 194:
OC4PTOC (51/67)
Function
Setting range
Accuracy
Trip current
(5-2500)% of
lBase
±
1.0% of I
n
at I ≤ I
n
±
1.0% of I at I > I
n
Reset ratio
> 95% at (50–2500)% of
lBase
-
Min. operating current
(1-10000)% of
lBase
±
1.0% of I
n
at I ≤ I
n
±
1.0% of I at I > I
n
Relay characteristic angle (RCA)
(40.0–65.0) degrees
±
2.0 degrees
Relay operating angle (ROA)
(40.0–89.0) degrees
±
2.0 degrees
2nd harmonic blocking
(5–100)% of fundamental
±
2.0% of I
n
Independent time delay at 0 to 2 x
I
set
(0.000-60.000) s
±
0.2 % or
±
35 ms whichever is
greater
Minimum trip time
(0.000-60.000) s
± 2.0 % or ± 40 ms whichever is
greater
Inverse characteristics, see
16 curve types
See table
and table
Trip time, pickup non-directional
at 0 to 2 x I
set
Min. = 15 ms
Max. = 30 ms
Reset time, pickup non-directional
at 2 to 0 x I
set
Min. = 15 ms
Max. = 30 ms
Critical impulse time
10 ms typically at 0 to 2 x I
set
-
Impulse margin time
15 ms typically
-
7.3
Instantaneous residual overcurrent protection EFPIOC
(50N)
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Instantaneous residual overcurrent
protection
EFPIOC
IN>>
IEF V1 EN
50N
Section 7
1MRK505222-UUS C
Current protection
396
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...